2001-01-08 00:00:00**********DENIED***********************
  
 1) MOP CLOSET TO HAVE EXHAUST PROVIDED
 PER 1997 SMC 503.1
 2) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62.89
 3) AIR BALANCE SCHEDULE REQUIRED PER
 1997 SMC 501.2