| Plan Review Notes For Permit 00051298 |
| Permit Number |
00051298 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) CODE INFORMATION BOX INCORRECT, BOX | | | SHOULD READ NFPA 101, 1985 EDITION | | | INSTEAD OF NFPA 101, 1991 | | | 2) SUBMIT COMPLETE SHOP DRAWINGS FOR | | | THE AUTOMATIC FIRE SPRINKLER SYSTEM | | | INSTALLATION. | | | 3) SUBMIT COMPLETE SHOP DRAWINGS FOR | | | THE FIRE ALARM SYSTEM. | | | 4) NO OPEN FLAMES ALLOWED IN STORE | | | WHEN OPENED PER CITY CODE, SEC 11-73 | | | 5) TRAVEL DISTANCES TO EXITS SHALL NOT | | | EXCEED 150 FEET. | | | 6) INTERIOR FINISH CLASS A OR B. | | | 7) EXITING THROUGH STOCKROOM PERMITTED | | | NOT MORE THAN 50 PERCENT | | | STOCKROOM NOT LOCKED | | | MAIN AISLE NOT LESS THAN 44 INCHES | | | PATH OF TRAVEL DEFINED | | | 8) OCCUPANT LOAD 30 SQ FEET PER PERSON | | | STOCKROOM 300 SQ FEET PER PERSON | | | PLANS REVIEWED BY LT. CARSILLO |
|