| Plan Review Notes For Permit 00051298 |
| Permit Number |
00051298 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | FIRST PLAN CHECK 6/2/00 | | | 1. SUBMIT STATE OF FLORIDA ENERGY FORM | | | SIGNED AND SEALED BY A PE. OR RA. | | | 2. SUBMMIT FIRE SPRINKLER PERMIT | | | 3. ALL GLAZING INSTALLED BY THE TENNANT | | | SHALL BE IMPACT RESISTANT GLAZING AND | | | BE APPROVED BY METRO DADE COUNTY OR SBCC | | | 4. DESIGNER OF RECORD TO RESEAL PLANS | | | SEVERAL SHEETS ARE NOT EMBOSSED TO ALLOW | | | THEM TO BE READ. | | | 5.SIGNS ARE NOT COVERED BY THIS PERMIT. | | | 6. CONTRACTOR TO SUBMIT PERMIT | | | APPLICATION AND PAY ALL FEES DUE. | | | 7. REVISE SHEET A0.1 CODE REFERENCES. | | | TO REFLECT PROPER CODES. | | | 1997 STANDARD BUILDING, MECHANICAL AND | | | GAS CODES | | | 1999 NATIONAL ELECTRICAL CODE | | | 1997 FLORIDA ACCESSABILITY CODE | | | 1994 STANDARD FIRE CODE IS NOT ADOPTED | | | DO NOT REFERENCE | | | 1985 LIFE SAFETY CODE | | | SSTD-12-97 |
|