| Plan Review Notes For Permit 00051297 |
| Permit Number |
00051297 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)TWO WAY CLEANOUTS SHALL BE INSTALLED | | | ON THE INLET AND OUTLET OF THE GREASE | | | INTERCEPTOR.(SEE ATTACHED DETAIL) | | | | | | 2)SHT.ENG.-3-THE CLEANOUT ON THE OUTLET | | | SIDE OF THE GREASE TRAP SHALL BE LOCATED | | | IN THE DISCHARGE LINE.AS DESIGNED THERE | | | IS A SECTION OF PIPE FROM THE TRAP THAT | | | CANNOT BE RODDED.SPC SEC.710.4. | | | | | | 3)TWO WAY CLEANOUTS ARE REQD.IN THE | | | INLET AND OUTLET.SEE DIAGRAM. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|