| Plan Review Notes For Permit 00051297 |
| Permit Number |
00051297 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1. ENGINEER TO PROVIDE LETTER INDICATING | | | 1/4" ROOF SLOPE AS PER CODE. OK 6/6/00 | | | 2. ROOFING SYSTEM SHALL MEET THE | | | REQUIREMENTS OF APPENDIX F FOR FIRST | | | FIRE DISTRICT.OK 6/6/00 | | | 3. FLORIDA ENERGY SHEETS REQUIRED.OK 6/6 | | | 4. SHEET S-3 MEZZANINE DESIGNED FOR | | | 50PSF. PLANS SHOW THAT THE AREA IS TO BE | | | USED FOR PUBLIC SEATING THUS 100PSF | | | REQUIRED SEE TABLE 1604.1, 1997 SBC.OK6/ | | | 5. SHEET A-1 WINDOWS AND DOORS SUBMIT | | | INFORMATION CERTIFYING CODE COMPLIANCE | | | TO 1997 SBC, SECTION 1006.2.4, 3/4 HOUR | | | FIRE RATING.OK 6/6/00 | | | 6. ALL EXTER GLAZING, SUBMIT PRODUCT | | | APPROVAL INFORMATION FOR LARGE MISSLE | | | IMPACT. SBCCI OR DADE COUNTY.OK 6/6/00 | | | 7. SIGNS AND AWNINGS REQUIRE SEPERATE | | | PERMITS. | | | 8. NO INTERIOR WORK IS COVERED BY THIS | | | PERMIT. | | | | | | INFORMATION CONTACT JOHN STANDBERG AT | | | 561-988-4002. |
|