| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-CONNECTORS SPECIFIED ON NEW DRAWINGS |
| | BY TURQUOISE, INC ARE NOT CORRECT. |
| | CHECK SEMCO CATALOGUE AND SPECIFY |
| | PROPER CONNECTORS. SEE PLANS FOR |
| | COMMENTS. |
| | 2-SECTION A-A SHOWS CONNECTORS FOR |
| | RAFTERS AT FLAT ROOF ONLY. |
| | SPECIFY CONNECTORS FOR NEW TRUSSES. |
| | 3-SPECIFY HOW IS CROSS VENTILATION FOR |
| | NEW ATTIC ACHIEVED. |
| | SEE SECTION 2309.7 SBC 1997. |
| | 4-CONNECTORS SPECIFIED FOR ROOF TRUSSES |
| | DON'T HAVE ANY ENGINEERED VALUE FOR |
| | LATERAL FORCES. SEE ANCHOR CATALOGUE |
| | AND ENGINEERED TRUSS. |
| | SPECIFY ANCHOR WITH VALUES FOR UPLIFT |
| | AND LATERAL FORCES AS REQUIRED. |
| | 5-SPECIFY ANCHORING OF GABLE END TRUSS. |
| | SEE ENGINEERED TRUSS. |
| | 6-ROOF TRUSSES: |
| | -THERE ARE 2 DIFFERENT TRUSS COMPANIES. |
| | DECIDE WHICH ONE IS GOING TO BE USED. |
| | -TRUSS DRAWINGS TO BE UPDATED & CLEARLY |
| | SPECIFY IF USING ASCE 7-95 FOR 145 MPH |
| | WIND LOAD OR SBC 1997 FOR 110 MPH WIND |
| | LOAD. |
| | -TRUSS LAYOUT AND ENGINEERED TRUSSES TO |
| | BE SIGNED, SEALED AND DATED AND WITH |
| | INFORMATION REQUIRED BY CHAPTER 471 OF |
| | FLORIDA STATUTES WHEN SUBMITTING |
| | DOCUMENTS FOR PUBLIC RECORDS. |
| | -PROFESSIONAL OF RECORD TO REVIEW ALL |
| | TRUSS DRAWINGS PRIOR TO SUBMITTAL TO |
| | THIS OFFICE. |
| | 7-PROVIDE PRODUCT APPROVALS FOR: |
| | -OUTSWING FRENCH DOORS. |
| | -OUTSWING DOOR AT KITCHEN. |
| | -INSWING DOOR AT BATH. |
| | -SINGLE HUNG WINDOW. |
| | -FLAT ROOF SYSTEM. |
| | -SHINGLES. |
| | 8-STORM PANELS: |
| | -PROVIDE PRODUCT APPROVAL. |
| | -PROVIDE A COMPLETE INSTALLATION |
| | SCHEDULE AS PER CITY SAMPLE ATTACHED |
| | AND A KEY PLAN. |
| | -CLEARLY INDICATE ON STORM PANELS DWGS |
| | THE MOUNTING METHOD AND ANCHOR AND |
| | SPACING TO BE USED ACCORDINT TO THE |
| | STRUCTURE TO BE ATTACHED TO. |
| | 9-SEE ADDITIONAL COMMENTS ON PLANS, |
| | INCLUDING COMMENTS BY THE OTHER TRADES |
| | 10-CONTRACTOR NEEDS TO UPDATE LICENSE. |
| | |
| | |
| | |
| | |
| | NOTES: |
| | |
| | 1-SEPARATE PERMITS AND FEES WILL BE |
| | REQUIRED FOR MECHANICAL, ELECTRICAL, |
| | PLUMBING AND ROOFING. |
| | 2-RETURN REVIEWED SET AFTER CORRECTIONS |
| | ARE DONE TO ORIGINAL DRAWING IN ORDER |
| | TO EXPEDITE THE REVIEW PROCESS. |