2001-01-08 00:00:00SECOND CHECKLIST:
 1-SPECIFY THE STAIR PROTECTION AS PER
 SECTION 1006 SBC 1997.
 2-SPECIFY STAIRWAY FIRE RATING.
 TABLE 705.1.2 SBC 1997.
 3-OFFICE/STORAGE AT NORTH CORNER IS
 ANOTHER USE. NEED TENANT SEPARATION.
 -PROVIDE TENANT SEPARATION BETWEEN THE
 TWO USES. SECTION 704 SBC 1997.
 -OFFICE TO HAVE RESTROOM.
  
  
  
  
 4-SAFETY GLASS. SECTION 2405.2 SBC 1997.
 DOORS WHERE NOT ERASED. ALTERNATIVELY,
 YOU MAY USE BY PASS DOORS AT CLOSETS.
 5-DOORS BY THE STAIRWAY NEED TO BE FIRE
 RATED AND SELF-CLOSING. TABLE 705.1.2
 SBC 1997.
 6-PROVIDE A COMPLETE WINDOW AND DOOR
 SCHEDULE IN ORDER TO ACCURATELY REVIEW
 COMPLIANCE WITH TABLE 600 SBC 1997 AND
 EGRESS REQUIREMENTS.
 -IN ADDITION PROVIDE BUILD'G DIMENSIONS
 AND INTERIOR HEIGHTS TO DETERMINE THE
 TOTAL BUILDING WALL AREA & PERCENTAGE
 OF OPENINGS ALLOWED AT NORTH ELEVATION
 BY TABLE 600 SBC 1997.
 7-CLARIFY WHY THERE IS AN OPENING FROM
 THE COMMERCIAL SPACE TO THE EGRESS
 STAIRWAY ENCLOSURE.
  
  
  
  
  
  
 * IF YOU HAVE ANY QUESTIONS PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT
 659-8096 EXT. 8232.