| Plan Review Notes For Permit 00051291 |
| Permit Number |
00051291 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SECOND CHECKLIST: | | | 1-SPECIFY THE STAIR PROTECTION AS PER | | | SECTION 1006 SBC 1997. | | | 2-SPECIFY STAIRWAY FIRE RATING. | | | TABLE 705.1.2 SBC 1997. | | | 3-OFFICE/STORAGE AT NORTH CORNER IS | | | ANOTHER USE. NEED TENANT SEPARATION. | | | -PROVIDE TENANT SEPARATION BETWEEN THE | | | TWO USES. SECTION 704 SBC 1997. | | | -OFFICE TO HAVE RESTROOM. | | | | | | | | | | | | | | | 4-SAFETY GLASS. SECTION 2405.2 SBC 1997. | | | DOORS WHERE NOT ERASED. ALTERNATIVELY, | | | YOU MAY USE BY PASS DOORS AT CLOSETS. | | | 5-DOORS BY THE STAIRWAY NEED TO BE FIRE | | | RATED AND SELF-CLOSING. TABLE 705.1.2 | | | SBC 1997. | | | 6-PROVIDE A COMPLETE WINDOW AND DOOR | | | SCHEDULE IN ORDER TO ACCURATELY REVIEW | | | COMPLIANCE WITH TABLE 600 SBC 1997 AND | | | EGRESS REQUIREMENTS. | | | -IN ADDITION PROVIDE BUILD'G DIMENSIONS | | | AND INTERIOR HEIGHTS TO DETERMINE THE | | | TOTAL BUILDING WALL AREA & PERCENTAGE | | | OF OPENINGS ALLOWED AT NORTH ELEVATION | | | BY TABLE 600 SBC 1997. | | | 7-CLARIFY WHY THERE IS AN OPENING FROM | | | THE COMMERCIAL SPACE TO THE EGRESS | | | STAIRWAY ENCLOSURE. | | | | | | | | | | | | | | | | | | | | | * IF YOU HAVE ANY QUESTIONS PLEASE FEEL | | | FREE TO CONTACT JULIO GOMEZ AT | | | 659-8096 EXT. 8232. |
|