| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING STAMPED DRAWINGS AND RECEIPT. |
| | 2-PROVIDE SAFETY GLASS AS REQUIRED. SEE |
| | PLANS FOR COMMENTS. SEC 2405.2 SBC/97. |
| | 3-PROVIDE A COMPLETE WINDOW AND DOOR |
| | SCHEDULE (NEW AND EXISTING). |
| | NOTE: KEEP IN CONSIDERATION EGRESS |
| | REQUIREMENTS FOR RESIDENTIAL AND FOR |
| | MIXED USE. (RESIDENTIAL AND BUSINESS). |
| | 4-PROVIDE COMPLETE DETAILS AND SPECS |
| | SHOW'G THE FIRE RESISTANCE SEPARATIONS |
| | REQUIRED AT FLOOR ASSEMBLY AND TENANT |
| | WALL SEPARATIONS (OFFICE/APARTMENT) |
| | SECTION 704 SBC 1997. |
| | 5-SPECIFY THE STAIR PROTECTION AS PER |
| | SECTION 1006 SBC 1997. |
| | -PROVIDE DETAILS AND SPECIFICATIONS FOR |
| | COMPLIANCE WITH SECTION 1007.5 FOR |
| | HANDRAILS. |
| | 6-PROVIDE COMPLETE HVAC DRAWINGS AND |
| | ENERGY CALCULATIONS AND MANUAL J CALCS |
| | AS REQUIRED. |
| | 7-PROVIDE COMPLETE INFORMATION TO ALLOW |
| | CALCULATION OF PERCENTAGE OF OPENINGS |
| | ALLOWED AT NORTH ELEVATION AS PER |
| | TABLE 600 SBC 1997. |
| | 8-WHERE IS THE RESTROOM FOR INDEPENDENT |
| | OFFICE. |
| | 9-CLEARLY SPECIFY ALL SCOPE OF WORK TO |
| | BE DONE IN ORDER TO DETERMINE A MORE |
| | ACCURATE VALUATION OF THE PROJECT OR |
| | PROVIDE COPY OF CONSTRUCTION CONTRACT. |
| | 10-PROVIDE SMOKE DETECTOR AT FIRST FLOOR |
| | SECTION 905.2.2 SBC 1997. |
| | NOTE: |
| | PLEASE RETURN REVIEWED SET AFTER ALL |
| | CORRECTIONS ARE DONE TO EXPEDITE THE |
| | REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT JULIO GOMEZ, BUILDING PLAN |
| | REVIEWER, AT 659-8096 X 8232. |