Plan Review Notes
Plan Review Notes For Permit 00051291
Permit Number 00051291
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-PROVIDE SAFETY GLASS AS REQUIRED. SEE
 PLANS FOR COMMENTS. SEC 2405.2 SBC/97.
 3-PROVIDE A COMPLETE WINDOW AND DOOR
 SCHEDULE (NEW AND EXISTING).
 NOTE: KEEP IN CONSIDERATION EGRESS
 REQUIREMENTS FOR RESIDENTIAL AND FOR
 MIXED USE. (RESIDENTIAL AND BUSINESS).
 4-PROVIDE COMPLETE DETAILS AND SPECS
 SHOW'G THE FIRE RESISTANCE SEPARATIONS
 REQUIRED AT FLOOR ASSEMBLY AND TENANT
 WALL SEPARATIONS (OFFICE/APARTMENT)
 SECTION 704 SBC 1997.
 5-SPECIFY THE STAIR PROTECTION AS PER
 SECTION 1006 SBC 1997.
 -PROVIDE DETAILS AND SPECIFICATIONS FOR
 COMPLIANCE WITH SECTION 1007.5 FOR
 HANDRAILS.
 6-PROVIDE COMPLETE HVAC DRAWINGS AND
 ENERGY CALCULATIONS AND MANUAL J CALCS
 AS REQUIRED.
 7-PROVIDE COMPLETE INFORMATION TO ALLOW
 CALCULATION OF PERCENTAGE OF OPENINGS
 ALLOWED AT NORTH ELEVATION AS PER
 TABLE 600 SBC 1997.
 8-WHERE IS THE RESTROOM FOR INDEPENDENT
 OFFICE.
 9-CLEARLY SPECIFY ALL SCOPE OF WORK TO
 BE DONE IN ORDER TO DETERMINE A MORE
 ACCURATE VALUATION OF THE PROJECT OR
 PROVIDE COPY OF CONSTRUCTION CONTRACT.
 10-PROVIDE SMOKE DETECTOR AT FIRST FLOOR
 SECTION 905.2.2 SBC 1997.
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER ALL
 CORRECTIONS ARE DONE TO EXPEDITE THE
 REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT JULIO GOMEZ, BUILDING PLAN
 REVIEWER, AT 659-8096 X 8232.