| 2001-01-08 00:00:00 | *************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SUBMIT PANEL SCHEDULES |
| | SHOWING THE REQ`D DEDICATED BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. MUST BE #12 |
| | AWG, AND 20 AMP.REVISED PANEL SCHEDULES |
| | BEFORE FINAL ELECTRICAL INSPECTION. |
| | 2)NOTE: PLEASE NOTE THAT THE USE IS |
| | RESIDENTIAL. SO OUTLET SPACING NEEDS TO |
| | MEET CODE. 210-522`,6`,12` RULE. NOTE |
| | MISSING OUTLETS FOR 2` OF WALL. ETC. |
| | |
| | 3)NOTE: PLEASESHOW THE REQ`D MEANS OF |
| | EGRESS LIGHTING FOR THE TWO DOORS SHOWN. |
| | PER 210-70. IF THERE IS EXISTING LIGHT- |
| | ING, PLEASE SHOW. |
| | |
| | 4)NOTE: ALL OUTLETS SERVING KITCHEN |
| | COUNTERSPACE ARE TO BE GFI/GFI PROTECTED |
| | PER 210-8-A-6 |
| | |
| | 5)NOTE: YOU ARE SHOWING FRONT OFFICE/DEN |
| | THESE ARE ROOMS THAT ARE ADAPTABLE TO |
| | SLEEPING ROOMS. PLEASE INCLUDE SMOKE |
| | DETECTORS INSIDE AND OUTSIDE. PLEASE |
| | SHOW THE USE OF THE FIRST FLOOR AS TO |
| | WHERE FRONT STEPS ARE GOING? SMOKE |
| | DETECTOR WILL BE REQ`D ON LOWER LANDING. |
| | NFPA-72 2-2.1.1.1 |
| | |
| | 6)NOTE: IF FRONT APT IS SEPARATE TENAT |
| | SPACE? THEN THE PANEL IN REAR APT. MAY |
| | NOT BE IN THERE. PANELS MUST BE INSTALL- |
| | -ED IN THAT SPACE. |
| | |
| | 7)NOTE: PLEASE SHOW FIRST FLOOR OCCP. |
| | 8)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR EXISTING PANLES/SERVICE. 215-5 |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8372 |