2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 SHOWING THE REQ`D DEDICATED BATH(S)
 CIRCUIT(S) PER 210-11-C-3. MUST BE #12
 AWG, AND 20 AMP.REVISED PANEL SCHEDULES
 BEFORE FINAL ELECTRICAL INSPECTION.
 2)NOTE: PLEASE NOTE THAT THE USE IS
 RESIDENTIAL. SO OUTLET SPACING NEEDS TO
 MEET CODE. 210-522`,6`,12` RULE. NOTE
 MISSING OUTLETS FOR 2` OF WALL. ETC.
  
 3)NOTE: PLEASESHOW THE REQ`D MEANS OF
 EGRESS LIGHTING FOR THE TWO DOORS SHOWN.
 PER 210-70. IF THERE IS EXISTING LIGHT-
 ING, PLEASE SHOW.
  
 4)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECTED
 PER 210-8-A-6
  
 5)NOTE: YOU ARE SHOWING FRONT OFFICE/DEN
 THESE ARE ROOMS THAT ARE ADAPTABLE TO
 SLEEPING ROOMS. PLEASE INCLUDE SMOKE
 DETECTORS INSIDE AND OUTSIDE. PLEASE
 SHOW THE USE OF THE FIRST FLOOR AS TO
 WHERE FRONT STEPS ARE GOING? SMOKE
 DETECTOR WILL BE REQ`D ON LOWER LANDING.
 NFPA-72 2-2.1.1.1
  
 6)NOTE: IF FRONT APT IS SEPARATE TENAT
 SPACE? THEN THE PANEL IN REAR APT. MAY
 NOT BE IN THERE. PANELS MUST BE INSTALL-
 -ED IN THAT SPACE.
  
 7)NOTE: PLEASE SHOW FIRST FLOOR OCCP.
 8)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR EXISTING PANLES/SERVICE. 215-5
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372