2001-01-08 00:00:00SUBMIT OCCUPANT LOAD BASED ON SQUARE
 FEET OF HABITABLE FLOOR SPACE.SEE SPC
 SEC.407.1.3.FOR ALLOWED DEDUCTIBLE AREAS
  
 SHT.A6.1-TOILET PAPER DISPENSER SHALL BE
 MOUNTED A MIN.19"TO CENTER PER FACBC
 FIG.29(B).
  
 SHT.A6.1-URINAL SHALL BE MOUNTED A MAX.
 OF 17"A.F.F.TO THE RIM PER FACBC SEC.
 4.18.2.
  
 SHT.A6.1-A MIN.OF 29"IS REQD.UNDER THE
 LAV.PER FACBC SEC.4.19.2.
  
 SHT.A6.2-FITTING ROOMS SHALL COMPLY W/
 FACBC SECS.4.1.3(21), 4.35.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 SUPPLY FIXED LADDERFOR ACCESS OR
 RELOCATE TO FLOOR.SPC 501.7.
  
 VENTS FOR FLOOR DRAINS SHALL COMPLY W/
 SPC SEC.906.2.2.
  
 MIN.SIZE DRAIN UNDERGROUND SHALL BE 2"
 PER SPC SEC.714.4.