| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD BASED ON SQUARE | | | FEET OF HABITABLE FLOOR SPACE.SEE SPC | | | SEC.407.1.3.FOR ALLOWED DEDUCTIBLE AREAS | | | | | | SHT.A6.1-TOILET PAPER DISPENSER SHALL BE | | | MOUNTED A MIN.19"TO CENTER PER FACBC | | | FIG.29(B). | | | | | | SHT.A6.1-URINAL SHALL BE MOUNTED A MAX. | | | OF 17"A.F.F.TO THE RIM PER FACBC SEC. | | | 4.18.2. | | | | | | SHT.A6.1-A MIN.OF 29"IS REQD.UNDER THE | | | LAV.PER FACBC SEC.4.19.2. | | | | | | SHT.A6.2-FITTING ROOMS SHALL COMPLY W/ | | | FACBC SECS.4.1.3(21), 4.35. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | SUPPLY FIXED LADDERFOR ACCESS OR | | | RELOCATE TO FLOOR.SPC 501.7. | | | | | | VENTS FOR FLOOR DRAINS SHALL COMPLY W/ | | | SPC SEC.906.2.2. | | | | | | MIN.SIZE DRAIN UNDERGROUND SHALL BE 2" | | | PER SPC SEC.714.4. |
|