| Plan Review Notes For Permit 00051268 |
| Permit Number |
00051268 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ACCEPTED BY REVISION 7/20/00 *********** | | | | | | | | | FLORIDA ENERGY CODE REQUIRES ALL AIR | | | DISTRIBUTION COMPONENTS TO BE INSULATED | | | PER 410.1.ABCD2.1 INCLUDES TOP SIDES OF | | | DIFFUSERS | | | ASHRAE 62-89 TABLE 2 PROVIDES REQUIRE- | | | MENTS FOR OUTSIDE AIR. THIS SPACE DOES | | | NOT MEET CRITERIA FOR REDUCING QUANTITY | | | OF OUTSIDE AIR BY CO2 SENSOR | | | 6.1.3 2. STATES WHERE OCCUPANCY DIFFERS | | | FROM TABLE 2, ETC. THERE IS A SPECIFIC | | | TABLE APPLICATION FOR THIS FACILITY TYPE | | | PROVIDE ASHRAE 62-89 TABLE 2 QUANTITY OF | | | OUTSIDE AIR FOR SPACE | | | NOTE: NFPA 90A REQUIRES NOTIFICATION OF | | | ACTIVIATION OF DUCT SMOKE DETECTOR BY | | | VISUAL AND AUDIBLE SIGNAL. THIS IS NOT | | | REQUIRED TO BE TIED TO THE MALL FIRE | | | ALARM SYSTEM |
|