2001-01-08 00:00:00ACCEPTED BY REVISION 7/20/00 ***********
  
  
 FLORIDA ENERGY CODE REQUIRES ALL AIR
 DISTRIBUTION COMPONENTS TO BE INSULATED
 PER 410.1.ABCD2.1 INCLUDES TOP SIDES OF
 DIFFUSERS
 ASHRAE 62-89 TABLE 2 PROVIDES REQUIRE-
 MENTS FOR OUTSIDE AIR. THIS SPACE DOES
 NOT MEET CRITERIA FOR REDUCING QUANTITY
 OF OUTSIDE AIR BY CO2 SENSOR
 6.1.3 2. STATES WHERE OCCUPANCY DIFFERS
 FROM TABLE 2, ETC. THERE IS A SPECIFIC
 TABLE APPLICATION FOR THIS FACILITY TYPE
 PROVIDE ASHRAE 62-89 TABLE 2 QUANTITY OF
 OUTSIDE AIR FOR SPACE
 NOTE: NFPA 90A REQUIRES NOTIFICATION OF
 ACTIVIATION OF DUCT SMOKE DETECTOR BY
 VISUAL AND AUDIBLE SIGNAL. THIS IS NOT
 REQUIRED TO BE TIED TO THE MALL FIRE
 ALARM SYSTEM