| Plan Review Notes For Permit 00051243 |
| Permit Number |
00051243 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATING | | | OF MAIN/PANEL. MIANS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9 | | | | | | 2)NOTE:PLEASE LIST THE REQ`D DEDICATED | | | BATH(S) CIRCUIT(S) AS PER 210-11-C-3 | | | MUST BE 20 AMP AND #12. | | | | | | 3)NOTE: PLEASE INCLUDE THE BLDG.STELL | | | OF BOTH NEW ADDITIONS AS PART OF THE | | | GROUNDING ELECTRODE SYSTEM AS REQ`D BY | | | 250-50 OF THE NEC/215-5 | | | | | | 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS IN DWELL- | | | -INGS. THE MAJORITY OF THE STRUCTURE | | | IS BEING WORKED ON (50)%. SD`S WILL BE | | | REQ`D IN EXISTING BEDROOM ALSO. ALL | | | MUST BE 120V AND WIRED IN SERIES. AS PER | | | NFPA-72 2-2.1.1.1. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|