2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE ATTIC ACCESS AT MAIN ROOF AND
 GUEST SUITE. SEC. 2309.6 SBC 1997.
 2-REVISE SIZE OF FOOTING F-1. SOIL TEST
 REPORT RECOMMENDS AN 18" WIDE FOOTING.
 F-1 CALLS FOR A 16" WIDE FOOTER.
 3-ENGINEERED TRUSSES:
 -UPDATE ALL GENERAL DETAILS AND
 LETTERS USING THE STANDARD BUILDING
 CODE (SBC) 1997 OR ASCE 7-95 AND
 ONLY THE ENGINEER WHO PREPARES
 THE DETAILS AND LETTERS SHALL
 SIGN, SEAL AND DATE THE DOCUMENT.
  
 -CLEARLY WRITE NAME, ADDRESS, LICENSE
 NUMBER AND TELEPHONE NUMBER OF
 ENGINEER PREPARING THE DOCUMENTS.
  
 4-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION SCHED.
 AS PER CITY SAMPLE AND UPDATE KEY PLAN
 TO MATCH ARCHITECT'S DRAWINGS.
 -CLEARLY INDICATE ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES (MEAN ROOF HEIGHT),
 PANEL SPAN, EDGE DISTANCE AND IF
 ANCHORED TO CONCRETE OR MASONRY.
 5-ENTRY DOOR PRODUCT APPROVAL REQUIRES
 A 2X BUCK. PROVIDE BUCK DETAIL WITH
 FASTENERS AS REQUIRED.