| Plan Review Notes For Permit 00051136 |
| Permit Number |
00051136 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | | NEW MAIN. MAINS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT.110-9/215-5 | | | | | | | | | | | | | | | | | | 3)NOTE: MUST BOND COLD WATER AT ADDITION | | | PER 250-50 PLEASE SHOW ON RISER DIAGRAM. | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | FOR SERVICE. ALL CONTINUOUS LOADS AT | | | 125%(LIGHTING) ETC. PLEASE SHOW LOAD | | | FOR TRACK LIGHTING PER 220-12B, SQ FT | | | PER 220. | | | | | | 5)NOTE;PER 250-50 BLDG STEEL MUST BE | | | BONDED AT ADDITION. | | | | | | 6)NOTE:PLEASE PROVIDE DISTANCE FROM | | | MAIN TO PANEL 'B' IN ADDITION. LENGTH | | | OF CONDUCTORS. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFOMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|