Plan Review Notes
Plan Review Notes For Permit 00051094
Permit Number 00051094
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT APPLICABLE SIZING CHART USED TO
 SIZE THE SYSTEM.SGC SEC.305.4.
  
 SUBMIT EHD NUMBER OF CSST TUBING FOR
 EACH SIZED BEING INSTALLED.SGC SEC.305.4
  
 SHOW PIPE CONNECTION TO METER,PIPE SIZE
 AND MATERIAL.SGC SEC.305.4.
  
 DISTANCE TO MOST REMOTE OUTLET SHALL BE
 SHOWN.SGC 305.4.
  
 SUBMIT DELIVERY PRESSURE TO SYSTEM.SGC
 305.4.
  
 INDICATE DISTANCE OF METER FROM HOUSE.
 COMPLY W/SGC 305.2.