2001-04-18 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL TO THIS
 OFFICE (USE THE REVIEW STAMP).
 2-TRUSS LAYOUT TO BE SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER. ALSO,
 PROVIDE ENGINEER'S INFORMATION AS
 REQUESTED BY CHAPTER 471 OF FLORIDA
 STATUTES WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
 3-SIMPSON STRONG-TIE LETTER SUBMITTED IS
 TOO OLD AND NEED TO BE SIGNED, SEALED
 AND DATED. CHAPTER 471 FL. STATUTES.
 4-UPDATE ALL GENERAL DETAILS PROVIDED.
 SIGN,SEAL, DATE PER CHAPTER 471 FL. ST
 5-CLARIFY WHY THERE ARE GENERAL DETAILS
 COPIES WITH THE SEALS OF DIFFERENT
 ENGINEERS. CHAPTER 471 FL. STATUTES.
 6-ENGINEER OF RECORD DESIGNED BUILDING
 BASED ON SBC 1997 FOR 110MPH. TRUSSES
 ARE DESIGNED BASED ON ASCE 7-93 FOR
 110MPH. MIXING OF PROVISIONS FROM ASCE
 AND SBC SHALL NOT BE PERMITTED. SEE
 SEC. 1606.1.2.1 OF SBC 97.
 -ENGINEERED TRUSSES SHALL BE DESIGNED
 USING SBC 1997 AND SHALL STATE THIS
 SPECIFIC CODE EDITION.
 -CLARIFY WHY TRUSS GE1 WAS DESIGNED
 USING SBC WHILE THE OTHERS ARE ASCE.
 7-TRUSSES V30, V26, V22, HV18 AND HV14
 ARE DESIGNED TO BEAR ON 3 SUPPORTS.
 PROVIDE DETAIL OR SPECIFICATIONS
 SHOWING HOW THE LOAD IS TRANSFERED
 THRU THE MIDDLE SUPPORT IF THERE IS NO
 MIDDLE SUPPORT SHOWN ON ROOF PLAN.
 ALSO, SPECIFY CONNECTORS TO RESIST THE
 CALCULATED UPLIFT LOADS.
  