Plan Review Notes
Plan Review Notes For Permit 00051083
Permit Number 00051083
Review Stop R
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-BEDROOM EGRESS WINDOWS TO HAVE 20" MIN
 CLEAR OPENING IN WIDTH, 24" MINIMUM
 CLEAR OPENING IN HEIGHT AND 5 SQUARE
 FEET MINIMUM CLEAR OPENING. SECTION
 1005.4 SBC 1997.
 2-STORM PANELS: CLEARLY INDICATE ON
 DRAWINGS WHICH ANCHOR AND SPACING IS
 GOING TO BE USED FOR THIS PROJECT FOR
 INSPECTOR'S INSPECTION.
 3-PROVIDE VENTILATION FOR FOR NEW
 BATHROOM AND EXISTING BATHROOM WHERE
 WINDOW WAS CLOSED.
 4-PROVIDE PRODUCT APPROVALS FOR:
 -EXTERIOR SWING DOOR (INCLUDE DRAWINGS)
 -ROOF SHINGLES FOR 110 MPH WIND LOAD.
 -SINGLE HUNG WINDOWS WITH COMPLETE AND
 LEGIBLE DRAWINGS.
 5-PROVIDE DENSITY LETTER AFTER SOIL IS
 COMPACTED.
 6-NEED TO APPLY FOR SEPARATE PERMITS FOR
 MECHANICAL, ELECTRICAL, PLUMBING AND
 ROOFING WORK. SUBCONTRACTORS DIDN'T
 APPLY FOR IT AT TIME OF BUILDING
 PERMIT APPLICATION.
  
  
  
  
  
  
 NOTES:
 -PROVIDE ALL REQUESTED INFORMATION PRIOR
 TO CONSTRUCTION OR INSTALLATION TO
 AVOID UNNECESSARY DELAYS.
 -IF YOU HAVE ANY QUESTIONS PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT 659-8096
 EXT. 8232.