| Plan Review Notes For Permit 00051083 |
| Permit Number |
00051083 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-BEDROOM EGRESS WINDOWS TO HAVE 20" MIN | | | CLEAR OPENING IN WIDTH, 24" MINIMUM | | | CLEAR OPENING IN HEIGHT AND 5 SQUARE | | | FEET MINIMUM CLEAR OPENING. SECTION | | | 1005.4 SBC 1997. | | | 2-STORM PANELS: CLEARLY INDICATE ON | | | DRAWINGS WHICH ANCHOR AND SPACING IS | | | GOING TO BE USED FOR THIS PROJECT FOR | | | INSPECTOR'S INSPECTION. | | | 3-PROVIDE VENTILATION FOR FOR NEW | | | BATHROOM AND EXISTING BATHROOM WHERE | | | WINDOW WAS CLOSED. | | | 4-PROVIDE PRODUCT APPROVALS FOR: | | | -EXTERIOR SWING DOOR (INCLUDE DRAWINGS) | | | -ROOF SHINGLES FOR 110 MPH WIND LOAD. | | | -SINGLE HUNG WINDOWS WITH COMPLETE AND | | | LEGIBLE DRAWINGS. | | | 5-PROVIDE DENSITY LETTER AFTER SOIL IS | | | COMPACTED. | | | 6-NEED TO APPLY FOR SEPARATE PERMITS FOR | | | MECHANICAL, ELECTRICAL, PLUMBING AND | | | ROOFING WORK. SUBCONTRACTORS DIDN'T | | | APPLY FOR IT AT TIME OF BUILDING | | | PERMIT APPLICATION. | | | | | | | | | | | | | | | | | | | | | NOTES: | | | -PROVIDE ALL REQUESTED INFORMATION PRIOR | | | TO CONSTRUCTION OR INSTALLATION TO | | | AVOID UNNECESSARY DELAYS. | | | -IF YOU HAVE ANY QUESTIONS PLEASE FEEL | | | FREE TO CONTACT JULIO GOMEZ AT 659-8096 | | | EXT. 8232. |
|