Plan Review Notes
Plan Review Notes For Permit 00051083
Permit Number 00051083
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 2-PROVIDE EGRESS AT BEDROOM. SEE SECTION
 1005.4 SBC 1997.
 3-PROVIDE COMPLETE BEAM AND LINTEL
 SCHEDULE WITH COMPLETE SPECS. ALSO,
 SPECIFY CONSTRUCTION OF WINDOW SILLS
 TO RECEIVE STORM PANELS.
 SECTION 104.2.2 CITY AMENDMENTS.
 4-NOTICE OF COMMENCEMENT NEEDS TO BE
 RECORDED WITH PALM BEACH COUNTY.
 5-PROVIDE SAFETY GLASS WHERE REQUIRED.
 SEE PLANS FOR COMMENTS. SECTION 2405.2
 SBC 1997.
 6-SEE PROVISO AND COMMENTS BY OTHER PLAN
 REVIEWERS.
 7-PROVIDE UPLIFT CALCULATIONS FOR ROOF
 TRUSSES. SEC 104.2.2 CITY AMENDMENTS.
 8-SPECIFY FIREBLOCKING WHERE REQUIRED.
 SECTION 2305 SBC 1997.
 9-ENGINEER TO CERTIFY THAT EXISTING ROOF
 TRUSSES AND CONNECTORS ARE ADEQUATE TO
 RECEIVE THE NEW ROOF LOADS AND
 REACTIONS. SEC 104.2.2 CITY AMENDMENTS
 10-PROVIDE CURRENT SIGNED, SEALED AND
 DATED SURVEY SHOWING THE ADDITION.
 11-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION,AS PER
 CITY SAMPLE ATTACHED, AND KEY PLAN.
 -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR SPACING ACCORDING TO THE
 DESIGN PRESSURES, PANEL SPAN, EDGE
 DISTANCE AND STRUCTURE TO BE ATTACHED
 12-CLARIFY IF THIS ADDITION IS GOING TO
 BE AIR CONDITIONED. IF SO, PROVIDE
 THE REQUIRED ENERGY CALCULATIONS.
 -IF NOT AIR CONDITIONING IS INSTALLED,
 THEN PROVIDE ADEQUATE VENTILATION AS
 PER SECTION 1203.4.2 SBC 1997.
 -PROVIDE LIGHT AND VENTILATION FOR
 BEDROOM AS PER SECTION 1203.1.2 SBC/97
 -PROVIDE A/C DRAWINGS FOR REVIEW.
 13-PROVIDE PRODUCT APPROVALS FOR:
 AWNING WINDOWS, EXTERIOR SWING DOOR,
 SLIDING GLASS DOORS, ROOF SHINGLES FOR
 A WIND VELOCITY OF 110 MPH.
 14-CLARIFY WHAT TYPE OF WINDOWS ARE
 GOING TO BE USED IN THIS HOUSE. AWNING
 WINDOWS OR SINGLE HUNG WINDOWS.
 15-PROVIDE COMPLETE ENGINEERED TRUSS
 DRAWINGS REVIEWED BY THE ENGINEER OF
 RECORD OF THIS ADDITION.
 16-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM:
 -MEAN ROOF HEIGHT IS INCORRECT.
 MEAN ROOF HEIGHT IS TAKEN FROM FINISH
 GRADE TO THE AVERAGE POINT OF THE
 HIGHEST ROOF.
 -COMPLETE BASIC VELOCITY PRESSURE. SEE
 TABLE 1606.2A SBC 1997.
 17-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC 1606 SBC 1997.
 18-OWES $51.29FOR RADON FEES AND
 BUILDING VALUATION. THIS IS TO BE PAID
 TO THE CITY OF WEST PALM BEACH. SEE
 ATTACHED PAYMENT RECEIPT.
  
  
  
 NOTE:
 PLEASE RETURN REVIEWED SETS IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.