Plan Review Notes
Plan Review Notes For Permit 00051083
Permit Number 00051083
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE:PLEASE SUBMIT LOAD CALCULATIONS
 FOR EXISTING SERVICE/HOUSE. PLEASE SHOW
 EXISTING SERVICE SIZE. PER 220-3-C-1 OF
 THE NEC.
  
 2)NOTE: PLEASE SUBMIT A PANEL SCHEDULE.
 ALSO PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) FOR RECEPT. MUST BE
 20AMP AND #12 PER 210-11-C-3
  
 3)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS OF NEW CONST-
 -RUCTION.
  
 4)NOTE:PLEASE NOTE THE MISSING OUTLET
 REQ`D FOR REAR OF DWELLING 210-52E
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT -
 8372