| 2001-01-08 00:00:00 | **************** PROVISO *************** | | | | | | 1)NOTE:PLEASE SUBMIT LOAD CALCULATIONS | | | FOR EXISTING SERVICE/HOUSE. PLEASE SHOW | | | EXISTING SERVICE SIZE. PER 220-3-C-1 OF | | | THE NEC. | | | | | | 2)NOTE: PLEASE SUBMIT A PANEL SCHEDULE. | | | ALSO PLEASE LIST THE REQ`D DEDICATED | | | BATH(S) CIRCUIT(S) FOR RECEPT. MUST BE | | | 20AMP AND #12 PER 210-11-C-3 | | | | | | 3)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS OF NEW CONST- | | | -RUCTION. | | | | | | 4)NOTE:PLEASE NOTE THE MISSING OUTLET | | | REQ`D FOR REAR OF DWELLING 210-52E | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMAITON | | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 EXT - | | | 8372 |
|