Plan Review Notes
Plan Review Notes For Permit 00051021
Permit Number 00051021
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT THE FOLLOWING INFORMATION FOR
 THE GAS INSTALLATION:
 1)SUBMIT A COPY OF/OR REFERENCE THE
 APPLICABLE GAS SIZING TABLE USED IN THE
 SIZING OF THE GAS SYSTEM.SGC 305.4.
  
 2)SHOW ALL CUT SECTIONS OF PIPE,TYPE OF
 PIPING MATERIAL,PIPE SIZES,TYPE OF GAS,
  
 3)DISTANCE TO MOST REMOTE OUTLET.
  
 4)DELIVERY PSI
  
 5)CALCULATIONS FOR COMBUSTION AIR PER
 NFPA 54 SEC.5.3.5 AND SGC SEC.402.4.
  
 6)DELIVERY PSI.
  
 7)TYPE LOCATION AND SIZE OF GAS VENTS.
  
 8)MANUF.SHEETS FOR ALL GAS EQUIPMENT.
  
 2)ONE MAIN VENT THRU ROOF IS REQD.PER
 SPC SEC.904.3.1.
  
 3)RISER S/1-WATER CLOSETS NOT PERMITTED
 ON WET VENTS PER COUNTYWIDE AMENDMENTS
 SEC.911.1.1.
  
 4)RISER S/1-DRY VENTS ARE NOT PERMITTED
 PER SPC SEC.906.2.1.
  
 5)RISER S/2-ONE MAIN VENT THRU ROOF IS
 REQD.PER SPC SEC.904.3.1.
  
 6)SHT.P100-GAS LINE FOR UNIT 1634 SHOWS
 A 3/4"LINE SUPPLYING A 1 1/2" LINE.
 COMPLY W/SGC SEC.305.4.
  
 7)SIZE THE WATER RISERS.
  
 8)WATER HEATERS SHALL BE READILY ACESS-
 IBLE PER SPC SEC.501.7.
  
 9)THE APPLICABLE PLUMBING CODE IS THE
 1994 EDITION,NOT THE 1995.