| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: YOU ARE SHOWING ON PANEL SCHED- | | | -ULES GFI RECEPT. CIRCUIT? IS THIS THE | | | REQ`D DEDICATED BATH RECEPT CIRCUIT? | | | IF SO PLEASE LIST ON PANEL SCHEDULE AS | | | BATH RECEPT. 210-11-C-3/215-5 | | | | | | 2)NOTE:PLEASE NOTE ON PANEL SCHEDULES | | | FOR UNITS B AND E YOU ARE SHOWING TWO | | | CIRCUITS,,,4 AND 6. ONE IS BEING SHOWN | | | AS SMALL APPLIANCE AND THE OTHER REC. | | | PLEASE INDICATE BOTH CIRCUITS AS SMALL | | | APPLIANCE AS REQ`D BY 210-11-C-1 | | | | | | 3)NOTE: PLEASE SHOW ON PLANS ALL THE | | | REQ`MENTS UNDER THE FAIR HOUSING ACT | | | REG.24 CFR 100.205 CHAPTER 5 | | | ALL THE HEIGHT REQ`MENTS FOR DEVICES | | | MUST BE SHOWN. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE 659-8096 EXT 8372 |
|