| Plan Review Notes For Permit 00051015 |
| Permit Number |
00051015 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT TOTAL LENGTH OF PIPE FROM POINT | | | OF DELIVERY THE MOST REMOTE OUTLET.SGC | | | SEC.305.4. | | | | | | SUBMIT TOTAL BTU LOAD ON THE SYSTEM | | | INCLUDING THE GRILL.SGC SEC.305.3. | | | | | | INDICATE SIZE OF PIPE SUPPLYING POOL | | | HEATER THAT WILL ALSO SUPPLY THE GRILL. | | | SGC SEC.302,305.4. | | | | | | INDICATE APPLICABLE GAS SIZING TABLE | | | FROM SGC FOR SYSTEM DESIGN. |
|