2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE: YOU HAVE SUBMITTED THE AIC RAT-
 -ING FOR BRANCH BREAKERS. HOW-EVER THE
 AIC RATING FOR MAIN IS REQ`D ALSO. MUST
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9.
  
 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS/ CORRELATE WITH PANEL SCHE-
 -DULE.
  
 3)NOTE PLEASE SUBMIT LOAD CALCULATION
 WITH ALL CONTINUOUS LOADS FIGURED AT
 125% (LIGHTING).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS