| Plan Review Notes For Permit 00051008 |
| Permit Number |
00051008 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO **************** | | | | | | 1)NOTE: YOU HAVE SUBMITTED THE AIC RAT- | | | -ING FOR BRANCH BREAKERS. HOW-EVER THE | | | AIC RATING FOR MAIN IS REQ`D ALSO. MUST | | | BE RATED FOR THE AVAILABLE FAULT CURRENT | | | PER 110-9. | | | | | | 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS/ CORRELATE WITH PANEL SCHE- | | | -DULE. | | | | | | 3)NOTE PLEASE SUBMIT LOAD CALCULATION | | | WITH ALL CONTINUOUS LOADS FIGURED AT | | | 125% (LIGHTING). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 |
|