2001-01-08 00:00:00*************BUILDING*************
  
 1]ALL EXTERIOR WALLS SHALL COMPLY WITH
 TABLE 600,SBC,REQUIREMENTS.SUBMIT
 APPROVED TESTED ASSEMBLY'S FOR 3HR WALL
 INCLUDE MIN. 18" PARAPET. NO OPENINGS
 ARE PERMITED WERE SPERATIONS OF LESS
 THAN 3' EXIST BETWEEN PROPERTY LINES OR
 OTHER BUILDINGS.
 2]SUBMIT COMPLETE CONSTRUCTION DETAILS
 FOR CONNECTION TO EXISTING BUILDING.
 3]PROVIDE ROOF DRAINAGE PLAN.
 4]A 2ND APPROVED EXIT IS REQUIRED,1004.2
 SBC.
 5]SUBMIT INTERIOR WALL SECTION.
 6]ADDITIONAL FEES OWED,COUNTY IMPACT FEE
 AND CITY RADON FEE.
  
  
  