| 2001-01-08 00:00:00 | *************** PROVISO **************** | | | | | | 1)NOTE: PLEASE CORRELATE PLANS SHOWING | | | PANEL #`S .ON E-1 AND E-2 YOU SHOW PANEL | | | H-3 AND H-4 WHICH ONE? OR IS THERE TWO? | | | PLEASE CORRECT.ASLO PLEASE SHOW PANEL | | | 'L-4' AS ALSO PANLE'L-3' IF THIS IS THE | | | CASE, AND PLEASE SHOW AS FEED-THRU-LUGS, | | | IF THIS IS THE CASE. | | | | | | 2)NOTE:PLEASE SHOW LOAD CALCULATION IN | | | DETAIL, SHOWING THE CONTINUOUS LOADS | | | FIGURED AT 125%. (LIGHTING ETC) | | | | | | 3)NOTE: PLEASE SHOW LOAD ON EXISTING | | | MDP AND THE ADDED LOAD FIGURED IN. 215-5 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE ANY ELECTRICAL INSPEC- | | | -TION IS CALLED IN. IF THERE IS ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|