Plan Review Notes
Plan Review Notes For Permit 00050965
Permit Number 00050965
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00***********PROVISO *******************
  
 1)NOTE: PLEASE SEE FIRST SET OF NOTES!
 PLEASE COMPLETE LOAD CALCULATIONS!!!!
 PLEASE SHOW THE CONTINUOUS LOADS AT 125%
  
 2)NOTE: PLEASE SEE RISER, STILL NEED TO
 SHOW WIRE SIZE FROM PANEL 'H' TO XFORMER
 I KNOW THE WIRE SIZE IS SHOWN ON PANEL
 SCHEDULE.
  
 3)NOTE: ALSO SIZE GROUND FOR TRANSFORMER
 PER 250-66. GROUNDING ELECTRODE.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372