| Plan Review Notes For Permit 00050965 |
| Permit Number |
00050965 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********PROVISO ******************* | | | | | | 1)NOTE: PLEASE SEE FIRST SET OF NOTES! | | | PLEASE COMPLETE LOAD CALCULATIONS!!!! | | | PLEASE SHOW THE CONTINUOUS LOADS AT 125% | | | | | | 2)NOTE: PLEASE SEE RISER, STILL NEED TO | | | SHOW WIRE SIZE FROM PANEL 'H' TO XFORMER | | | I KNOW THE WIRE SIZE IS SHOWN ON PANEL | | | SCHEDULE. | | | | | | 3)NOTE: ALSO SIZE GROUND FOR TRANSFORMER | | | PER 250-66. GROUNDING ELECTRODE. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|