| Plan Review Notes For Permit 00050965 |
| Permit Number |
00050965 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO PROVIDE MORE DETAIL ON | | | LOAD CALCULATIONS. GIVE BREAK DOWN AND | | | COMPLETE WHAT IS BEING SHOWN. PLEASE | | | SHOW ALL LOADS THAT ARE CONTINUOUS AT | | | 125%. LIGHTING? | | | | | | 2)NOTE: PLEASE SHOW WIRE SIZE FROM | | | PANEL 'H' TO TRANSFORMER. | | | | | | 3)NOTE: PLEASE PROVIDE AIC RATINGS FOR | | | ALL EQUIPMENT, MAINS, PANELS, BREAKERS. | | | PER 110-9 AND 215-5 | | | | | | 4)NOTE: PLEASE SHOW GROUNDING FOR TRANS- | | | -FORMER. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|