| 2001-01-08 00:00:00 | 1.MEN'S H.C. STALL DOESNOT HAVE REQUIRED | | | TURNING RADIUS. | | | 2.URINALS; MESSUREMENTS MUST BE INSIDE | | | TO INSIDE NOT CENTER OF PARTITION. | | | BOTH MESSUREMENTS ARE MINIMUM | | | EXCEPTABLE WIDTH. | | | 3.VACUUM RELIFE VALVE ON WATER HEATER | | | TO COMPLY TO MANUF. SPECIFICATIONS. | | | 4.PAGE P-3 WATER HEATER RISER DIAGRAM | | | CHANGE FLOOR DRAIN TO FLOOR SINK. | | | 5.AUTOMATIC SHUTOFF VALVES SHALL HAVE | | | A SHUTOFF VALVE UP STREAM AND UNIONS | | | SO AUTOMATIC VALVE CAN BE REPLACED | | | IF REQUIRED. | | | 6.GAS SHUTOFF VALVES FOR EACH PIECE OF | | | EQUIPMENT SHALL BE ACCESSIBLE WITHOUT | | | MOVING EQUIPMENT. |
|