| 2001-01-08 00:00:00 | 1)SUBMIT CALCULATIONS FOR COMBUSTION AIR |
| | PER SGC SEC.402.4,402.4.4. |
| | |
| | 2)SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP. |
| | EQUIPMENT SHALL BE LISTEDPER SGC SEC. |
| | 402.1. |
| | |
| | 3)SUBMIT DETAILS ON VENT FOR WATER HEAT- |
| | ER.COMPLY W/SGC SEC.607,608,AND VENTING |
| | TABLES IN SGC CHAPT.6. |
| | |
| | 4)CONTROLS FOR GAS EQUIPMENT SHALL |
| | COMPLY W/NFPA 54 SEC.5.5.4. |
| | |
| | 5)SHUT-OFF VALVES ARE REQD.ON THE BRANCH |
| | LINES OF THE WATER SUPPLY SYSTEM PER SPC |
| | SEC.610.4.2. |
| | |
| | 6)RELIEF LINES FROM WATER HEATER SHALL |
| | DRAIN TO FLOOR SINK NOT FLOOR DRAIN PER |
| | SPC SEC.807.1.3. |
| | |
| | 7)CONTACT R.COMPO W/CITY OF WEST PALM |
| | BEACH FOR APPROVAL OF THE GREASE TRAPS. |
| | SUBMIT COPY OF APPROVAL.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.101.4.7. |
| | |
| | 8)CLEAR FLOOR SPACE FOR WATER CLOSET IN |
| | WOMEN'S RESTROOM SHALL COMPLY W/FACBC |
| | SEC.4.17.3.& FIG.30. |
| | |
| | 9)SPECS.ON SHT.P1 CALL OUT A FLOOR |
| | MOUNTED WATER CLOSET AND THE PLANS SHOW |
| | A WALL MOUNTED WATER CLOSET.IF FLOOR |
| | MOUNTED THE H.C.TOILET STALL IN THE |
| | MEN'S RESTROOM DOESN'T COMPLY W/FACBC |
| | SEC.4.17.3 AND FIG.#30. |
| | |
| | 10)MAX.TEMPERATURE OF WATER DISCHARGED |
| | TO THE SANITARY SYSTEM SHALL BE 140 |
| | DEGREES PER SPC 717.8 |
| | |
| | 11)STANDARD URINAL REQS.A MIN. OF 24" |
| | CLEARANCE PER SPC SEC.403.4. |
| | |
| | 12)WATER CLOSETS ARE NOT PERMITTED ON |
| | WET VENTS PER COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.911.1.1. |
| | |
| | 13)OVER 2 FIXTURES SUPPLIED BY 1/2"C.W. |
| | SEE SHT.P5.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.607.7. |
| | |
| | 14)SIZE THE GAS LINES TO THE EQUIPMENT. |
| | COMPLY W/SGC TABLE 305.4(A). |
| | |
| | 15)AUTOMATIC SHUT-OFF VALVES SHALL BE |
| | ACCESSIBLE AND LOCATED BELOW CEILING. |
| | SGC 310.1. |
| | |
| | 16)THE APPLICABLE GAS CODE IN EFFECT IN |
| | THE CITY OF WPB IS THE 1997 STANDARD GAS |
| | CODE,NOT THE 1994. |
| | |
| | 17)DISHWASHER SHALL NOT DISCHARGE TO THE |
| | GREASY WASTE SYSTEM PER LOCAL ORDINANCE. |
| | DISCHARGE SHALL BE TO SANITARY SYSTEM. |
| | |
| | 18.)VACUUM RELIEF VALVES ARE REQD,ON ALL |
| | BOTTOM FED WATER HEATERS AND SHALL BE |
| | INSTALLED PER MANUF.RECOMMENDATIONS. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | QUESTIONS.TIMOTHY LARGE. |
| | PLUMBING PLANS EXAMINER. |