Plan Review Notes
Plan Review Notes For Permit 00050908
Permit Number 00050908
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:001)SUBMIT CALCULATIONS FOR COMBUSTION AIR
 PER SGC SEC.402.4,402.4.4.
  
 2)SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 EQUIPMENT SHALL BE LISTEDPER SGC SEC.
 402.1.
  
 3)SUBMIT DETAILS ON VENT FOR WATER HEAT-
 ER.COMPLY W/SGC SEC.607,608,AND VENTING
 TABLES IN SGC CHAPT.6.
  
 4)CONTROLS FOR GAS EQUIPMENT SHALL
 COMPLY W/NFPA 54 SEC.5.5.4.
  
 5)SHUT-OFF VALVES ARE REQD.ON THE BRANCH
 LINES OF THE WATER SUPPLY SYSTEM PER SPC
 SEC.610.4.2.
  
 6)RELIEF LINES FROM WATER HEATER SHALL
 DRAIN TO FLOOR SINK NOT FLOOR DRAIN PER
 SPC SEC.807.1.3.
  
 7)CONTACT R.COMPO W/CITY OF WEST PALM
 BEACH FOR APPROVAL OF THE GREASE TRAPS.
 SUBMIT COPY OF APPROVAL.COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.4.7.
  
 8)CLEAR FLOOR SPACE FOR WATER CLOSET IN
 WOMEN'S RESTROOM SHALL COMPLY W/FACBC
 SEC.4.17.3.& FIG.30.
  
 9)SPECS.ON SHT.P1 CALL OUT A FLOOR
 MOUNTED WATER CLOSET AND THE PLANS SHOW
 A WALL MOUNTED WATER CLOSET.IF FLOOR
 MOUNTED THE H.C.TOILET STALL IN THE
 MEN'S RESTROOM DOESN'T COMPLY W/FACBC
 SEC.4.17.3 AND FIG.#30.
  
 10)MAX.TEMPERATURE OF WATER DISCHARGED
 TO THE SANITARY SYSTEM SHALL BE 140
 DEGREES PER SPC 717.8
  
 11)STANDARD URINAL REQS.A MIN. OF 24"
 CLEARANCE PER SPC SEC.403.4.
  
 12)WATER CLOSETS ARE NOT PERMITTED ON
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.
  
 13)OVER 2 FIXTURES SUPPLIED BY 1/2"C.W.
 SEE SHT.P5.COUNTYWIDE AMENDMENTS TO SPC
 SEC.607.7.
  
 14)SIZE THE GAS LINES TO THE EQUIPMENT.
 COMPLY W/SGC TABLE 305.4(A).
  
 15)AUTOMATIC SHUT-OFF VALVES SHALL BE
 ACCESSIBLE AND LOCATED BELOW CEILING.
 SGC 310.1.
  
 16)THE APPLICABLE GAS CODE IN EFFECT IN
 THE CITY OF WPB IS THE 1997 STANDARD GAS
 CODE,NOT THE 1994.
  
 17)DISHWASHER SHALL NOT DISCHARGE TO THE
 GREASY WASTE SYSTEM PER LOCAL ORDINANCE.
 DISCHARGE SHALL BE TO SANITARY SYSTEM.
  
 18.)VACUUM RELIEF VALVES ARE REQD,ON ALL
 BOTTOM FED WATER HEATERS AND SHALL BE
 INSTALLED PER MANUF.RECOMMENDATIONS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.TIMOTHY LARGE.
 PLUMBING PLANS EXAMINER.