| 2001-01-08 00:00:00 | SHT.A0-THE APPLICABLE PLUMBING CODE IS |
| | THE 1994 EDITION OF THE STANDARD PLBG. |
| | CODE.COUNTYWIDE AMENDMENT TO SPC 101.1 |
| | AND FLA.STATUTE. |
| | |
| | PLANS SHALL BE ROUTED TO DEPT.OF |
| | BUSINESS REGULATION FOR REVIEW AND |
| | APPROVAL.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.101.4.7. |
| | |
| | SUBMIT SQ.FT.AREA OF HABITABLE FLOOR |
| | SPACE FOR DETERMINATION OF MIN.FIXTURE |
| | REQS.SEE SPC SEC.407.1.3.FOR ALLOWED |
| | DEDUCTIBLE AREAS. |
| | |
| | WALLS IN TOILET ROOMS SHALL BE |
| | NONABSORBENT TO A HEIGHT OF 4' PER SBC |
| | SEC.1204.2. |
| | |
| | SUBMIT A COMPLETE GAS DRAWING SHOWING |
| | ALL GAS PIPING AS A WHOLE ALONG W/THE |
| | FOLLOWING ITEMS: |
| | A COPY OF OR REFERENCE TO THE SPECIFIC |
| | GAS SIZING TABLE USED TO DESIGN THE |
| | SYSTEM. |
| | 2)SHOW DIMENSIONS OF ALL CUT SECTIONS OF |
| | PIPE,TYPE OF PIPING MATERIAL,ALL PIPE |
| | SIZES,TYPE OF GAS,ETC. |
| | 3)DISTANCE TO MOST REMOTE OUTLET. |
| | 4)DELIVERY PSI AT METER. |
| | 5)CALCULATIONS FOR COMBUSTION AIR. |
| | 6)TYPE,LOCATION,SIZE AND TERMINATION PT. |
| | OF GAS VENTS. |
| | 7)MANUF.SHEETS FOR ALL GAS EQUIP. |
| | (EQUIPMENT SHALL BE LISTED.SGC SEC.402.1 |
| | |
| | SUBMIT MORE INFORMATION/ISOMETRIC DRAW- |
| | ING ON AIR INTAKE AND EXHAUST PIPING FOR |
| | WATER HEATERS.(SEE SHT.P-3.) |
| | |
| | CONTROLS FOR GAS EQUIPMENT SHALL COMPLY |
| | W/NFPA 54 SEC.5.5.4. |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/SPC |
| | 610.4.1.,610.4.2. |
| | |
| | FLOOR SINKS SHALL BE USED IN KITCHEN |
| | AREA IN LIEU OF FLOOR DRAINS PER SPC |
| | SEC.807.1.3. |
| | |
| | INDIRECT WASTES SHALL COMPLY W/SPC SEC. |
| | 805.1,805.2. |
| | |
| | WASTES FROM BAR SINK AREAS SHALL DIS- |
| | CHARGE TO GREASE INTERCEPTOR PER SPC |
| | SEC.804.1.,1004.4. |
| | |
| | CONTACT R.COMPO W/CITY OF WEST PALM |
| | UTILITIES FOR CHANGES TO THE GREASY |
| | WASTE SYSTEM(SUBMIT APPROVAL FROM |
| | UTILITIES FOR EXISTING GREASE SYSTEM. |
| | |
| | CLEAR FLOOR SPACE FOR WATER CLOSET IN |
| | MEN'S RESTROOM SHALL COMPLY W/FACBC SEC. |
| | 4.16.2 AND FIGURE 28. |
| | |
| | SIZE OF VENTS SHALL COMPLY W/SPC SEC. |
| | 920.2.(SEE URINALS AND VENT FOR 6"DRAIN) |
| | |
| | URINAL IS LOCATED IN LINE OF SIGHT FROM |
| | VESTIBULE AREA.COMPLY W/SPC SEC.404.3. |