Plan Review Notes
Plan Review Notes For Permit 00050908
Permit Number 00050908
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***********DENIED***********************
  
 1) AIR BALANCE AND AIR CONDITIONING PLAN
 OK
 2) 1997 SMC 505.9.1 VERTICAL AND HORIZ-
 ONTAL DUCTS LOCATED IN BUILDINGS 2
 OR MORE STORIES SHALL BE ENCLOSED IN A
 CONTINUOUS ENCLOSURE FROM THE CEILING
 ABOVE THE HOOD TO OF THROUGH THE ROOF.
 505.9.2 REQUIRES THE ENCLOSURE TO BE
 USED EXCLUSIVELY TO ENCLOSE A SINGLE
 GREASE EXHAUST SYSTEM AND SHALL BE USED
 FOR NO OTHER PURPOSE.
 NOTE: SEPARATE PERMITS REQUIRED FOR HOOD
 WALK IN COOLER/FREEZER, AND FIRE SUPPRES
 SION FOR HOODS