| Plan Review Notes For Permit 00050908 |
| Permit Number |
00050908 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | | | | 1) AIR BALANCE AND AIR CONDITIONING PLAN | | | OK | | | 2) 1997 SMC 505.9.1 VERTICAL AND HORIZ- | | | ONTAL DUCTS LOCATED IN BUILDINGS 2 | | | OR MORE STORIES SHALL BE ENCLOSED IN A | | | CONTINUOUS ENCLOSURE FROM THE CEILING | | | ABOVE THE HOOD TO OF THROUGH THE ROOF. | | | 505.9.2 REQUIRES THE ENCLOSURE TO BE | | | USED EXCLUSIVELY TO ENCLOSE A SINGLE | | | GREASE EXHAUST SYSTEM AND SHALL BE USED | | | FOR NO OTHER PURPOSE. | | | NOTE: SEPARATE PERMITS REQUIRED FOR HOOD | | | WALK IN COOLER/FREEZER, AND FIRE SUPPRES | | | SION FOR HOODS |
|