| Plan Review Notes For Permit 00050908 |
| Permit Number |
00050908 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATINGS | | | OOR THE 600 AMP DISC AND 700 AMP BREAKER | | | ENCLOUSURE. 110-9/215-5 NEEDS TO BE ON | | | PLANS SUBMITTED. | | | | | | 2)NOTE: PLEASE NOTE THE OUTLET SPACING | | | REQ`MENT PER LOCAL CODE. 210-50 | | | EVERY 20` OF UNENCUMBERED WALL SPACE. | | | | | | | | | 3)NOTE:PLEASE SEE SHEET E-5 YOU SHOW | | | ON MAIN THE "SAMBA" BEING SERVED BY | | | TRKR #3 ? PLEASE CLARIFY. | | | | | | 4)NOTE: PLEASE SHOW WHAT/OR WHERE | | | "CHEFS PANEL" IS/ OR WHERE IT IS GOING | | | TO BE. | | | | | | 5)NOTE: PLEASE NOTE AND CHECK THE REQ`- | | | -MENTS OF ART; 450-21-B FORTRANSFORMER | | | ROOM? OVER 112 1/2 KVA. ALSO EXCEPT. #1 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASECALL 561-659-8096 EXT 8372 |
|