Plan Review Notes
Plan Review Notes For Permit 00050908
Permit Number 00050908
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATINGS
 OOR THE 600 AMP DISC AND 700 AMP BREAKER
 ENCLOUSURE. 110-9/215-5 NEEDS TO BE ON
 PLANS SUBMITTED.
  
 2)NOTE: PLEASE NOTE THE OUTLET SPACING
 REQ`MENT PER LOCAL CODE. 210-50
 EVERY 20` OF UNENCUMBERED WALL SPACE.
  
  
 3)NOTE:PLEASE SEE SHEET E-5 YOU SHOW
 ON MAIN THE "SAMBA" BEING SERVED BY
 TRKR #3 ? PLEASE CLARIFY.
  
 4)NOTE: PLEASE SHOW WHAT/OR WHERE
 "CHEFS PANEL" IS/ OR WHERE IT IS GOING
 TO BE.
  
 5)NOTE: PLEASE NOTE AND CHECK THE REQ`-
 -MENTS OF ART; 450-21-B FORTRANSFORMER
 ROOM? OVER 112 1/2 KVA. ALSO EXCEPT. #1
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASECALL 561-659-8096 EXT 8372