Plan Review Notes
Plan Review Notes For Permit 00050907
Permit Number 00050907
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:001.STOP GAS RISER AT METER. DELETE GAS
 SERVICE LINE AND COMMENT.
 2.TOTAL BTU'S TOTAL 1,389,000 3" PIPE
 REQUIRED FROM METER TO FIRST DROP.
 SHT. P-2 GAS PIPE SHOWN 3" ISO. SHOWS
 2 1/2"
 3.LIST GAS PIPE TYPE TO BE INSTALLED.
 4.SUBMIT MANUF. SHEETS FOR ALL GAS
 EQUIPMENT.
 5.CALCULATIONS FOR COMBUSTION AIR
 REQUIRED FOR WATER HEATERS.
 6.HANDYCAP STALLS DOES NOT COMPLY WITH
 FACBC SEC 4.17.3 AND FIG. 30
 7.CANNOT LOCATE DPR APPROVAL.
 8.W.H. VAC.BRACKER TO BE PIPED ABOVE
 WATER HEATERS.
 9.WASTE FROM 3 COMPARTMENT SINK IN
 BAR AREA TO BE PIPED TO GREASE INTER-
 CEPTOR.