| Plan Review Notes For Permit 00050907 |
| Permit Number |
00050907 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1.STOP GAS RISER AT METER. DELETE GAS | | | SERVICE LINE AND COMMENT. | | | 2.TOTAL BTU'S TOTAL 1,389,000 3" PIPE | | | REQUIRED FROM METER TO FIRST DROP. | | | SHT. P-2 GAS PIPE SHOWN 3" ISO. SHOWS | | | 2 1/2" | | | 3.LIST GAS PIPE TYPE TO BE INSTALLED. | | | 4.SUBMIT MANUF. SHEETS FOR ALL GAS | | | EQUIPMENT. | | | 5.CALCULATIONS FOR COMBUSTION AIR | | | REQUIRED FOR WATER HEATERS. | | | 6.HANDYCAP STALLS DOES NOT COMPLY WITH | | | FACBC SEC 4.17.3 AND FIG. 30 | | | 7.CANNOT LOCATE DPR APPROVAL. | | | 8.W.H. VAC.BRACKER TO BE PIPED ABOVE | | | WATER HEATERS. | | | 9.WASTE FROM 3 COMPARTMENT SINK IN | | | BAR AREA TO BE PIPED TO GREASE INTER- | | | CEPTOR. |
|