Plan Review Notes
Plan Review Notes For Permit 00050907
Permit Number 00050907
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:001)SHT.A0-THE APPLICABLE PLUMBING CODE
 IS THE 1994 EDITION OF THE STANDARD
 PLUMBING CODE,NOT 1997.
  
 2)SHOW THE CLEAR INSIDE DIMENSIONS(LXW)
 OF THE HANDICAP STALLS.COMPLY W/FACBC
 SEC.4.17.3,& FIG.30.
  
 3)SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR THE WATER HEATERS.SGC SEC.402.4.,
 402.4.4.
  
 4)SUBMIT DETAIL OF GAS VENT.SHOW TYPE,
 TERMINATION AND SIZE.SEE ATTACHED REQS.
 SUBMIT DETAILS FOR THE AIR INTAKE AND
 EXHAUST SYSTEMS FOR THE WATER HEATERS.
 COMPLY W/SGC CHAPT.6.SEE SHT.P-3.
  
 5)CONTROLS FOR GAS EQUIPMENT SHALL
 COMPLY W/NFPA 5.5.4.,SGC SEC.310.1.A
 MANUAL SHUT-OFF VALVE AND UNION SHALL BE
 INSTALLED AT CONTROLS FOR REMOVAL AND
 REPLACEMENT.VALVES SHALL BE LOCATED
 BELOW CEILING.
  
 6)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.2.(S.O.V.IS REQD.ON WATER
 SUPPLY BRANCH FROM MAIN.)
  
 7)CONTACT R.COMPO W/CITY OF WPB
 UTILITIES FOR CHANGES TO THE GREASY
 WASTE SYSTEM.(SUBMIT APPROVAL FROM
 UTILITIES FOR GREASE TRAP.)
  
 8)A FLOOR SINK IN LIEU OF THE FLOOR
 DRAIN SHALL BE INSTALLED TO RECEIVE THE
 DISCHARGE FROM THE P & T VALVE FROM THE
 WATER HEATER.SPC SEC.804.1,807.1.3.
  
 9)A VACUUM RELIEF VALVE IS REQD.ON
 BOTTOM FED WATER HEATERS PER SPC.507.1.2
  
 10)SHT.P-4-NOT MORE THAN 2 FIXTURES
 SHALL BE SUPPLIED BY 1/2" CW LINE.
 COUNTYWIDE AMENDMENTS TO SPC SEC.607.7.
  
 11)SHT.P-4-THE APPLICABLE GAS CODE IN
 EFFECT IN THE CITY OF WPB IS THE 1997
 STANDARD GAS CODE,NOT HTE 1994 EDITION.
  
 12)SHT.P-4-CLARIFY PSI FOR THE GAS
 SYSTEM.PLANS NOTE 25 PS1.THIS CANNOT BE
 CORRECT AS DESIGNED.COUNTYWIDE AMENDMENT
 TO SPC SEC.104.2.1.
  
 13)DISCHARGE OF EFFLUENT TO SANITARY
 SYSTEM SHALL NOT EXCEED 140 DEGREES
 UNLESS PROPER COOLING METHODS ARE
 INCORPORATED.SPC SEC.717.8.
  
 14.)DISHWASHER CANNOT DISCHARGE TO THE
 GREASY WASTE SYSTEM PER LOCAL ORDINANCE.
 DISCHARGE SHALL BE TO THE SANITARY
 SYSTEM.
  
 15)SHT.A-8-MEN'S TOILET ROOM-THE DOOR ON
 THE HANDICAP STALL SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQD.FOR THE LAV.
 COMPLY W/FACBC SEC.4.22.2.(SEE SHT.P-2
 ALSO).
  
 16)SIZE THE GAS LINES TO THE APPLIANCE.
 COMPLY W/TABLE 305.4(A).
  
 18)SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT
 EQUIPMENT SHALL BE LISTED PER SGC SEC.
 402.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.