Plan Review Notes
Plan Review Notes For Permit 00050907
Permit Number 00050907
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)SHT.A0-THE APPLICABLE PLUMBING CODE IS
 THE 1994 EDITION OF THE STANDARD PLUMB-
 ING CODE,NOT 1997.
  
 2)SHOW THE CLEAR INSIDE DIMENSIONS(LXW)
 OF THE HANDICAP TOILET STALLS.COMPLY W/
 FACBC SEC.4.17.3,FIG.30.
  
 3)THE GAS ISOMETRIC SHALL REFLECT THE
 FOLLOWING ITEMS.
 A)A COPY OF OR REFERENCE TO THE SPECIFIC
 GAS SIZING TABLE USED TO DESIGN THE
 SYSTEM.SGC 305.4
 B)SHOW DIMENSIONS OF ALL CUT SECTIONS OF
 PIPE,TYPE OF PIPING MATERIAL,ALL PIPE
 SIZES,TYPE OF GAS,ETC.
 C)DISTANCE TO MOST REMOTE OUTLET.
 D)DELIVERY PSI AT METER.
 E)CALCULATIONS FOR COMBUSTION AIR.
 F)TYPE,LOCATION AND SIZE OF GAS VENTS.
 G)MANUF.SHEETS FOR ALL GAS EQUIPMENT.
 (EQUIPMENT SHALL BE LISTED PER SGC SEC.
 402.1.)
  
 4)SUBMIT ADDITIONAL INFORMATION ON THE
 AIR INTAKE AND EXHAUST SYSTEMS FOR THE
 WATER HEATERS.(SEE SHT.P-3.)
  
 5)CONTROLS FOR GAS EQUIPMENT SHALL
 COMPLY W/ NFPA 5.5.4.,SGC 310.1.
 A MANUAL SHUT-OFF VALVE AND A UNION
 DOWNSTREAM SHALL BE INSTALLED AT
 CONTROLS FOR REMOVAL AND REPLACEMENT.
 VALVES SHALL BE LOCATED BELOW CEILING.
  
 6)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.2.(S.O.V.REQD.ON BRANCH
 MAIN).
  
 7)WASTES FROM THE BAR AREA SHALL DIS-
 CHARGE THROUGH THE GREASE INTERCEPTOR
 PER SPC 804.1,1004.4.
  
 8)CONTACT R.COMPO W/CITY OF WPB
 UTILITIES FOR CHANGES TO THE GREASY
 WASTE SYSTEM.(SUBMIT APPROVAL FROM
 UTILITIES FOR EXIST,GREASE TRAP.)
  
 9)A FLOOR SINK SHALL BE INSTALLED TO
 RECEIVE THE DISCHARGE FROM THE P & T
 VALVE
  
 10)A VACUUM RELIEF VALVE IS REQ,ON
 BOTTOM FED WATER HEATERS PER SPC SEC.
 507.1.2.
  
 11)SHT.P-4-NOT MORE THAN 2 FIXTURES CAN
 BE SUPPLIED BY 1/2"C.W.LINE.COUNTYWIDE
 AMENDMENTS TO SPC SEC.607.
  
 12)SHT.A8-MEN'S TOILET ROOM-H.C.STALL
 DOOR SWINGS INTO CLEAR FLOOR SPACE FOR
 LAV.COMPLY W/FACBC SEC.4.22.2.(SEE SHT.
 P2 ALSO).
  
 13)SHT.P4-THE APPLICABLE GAS CODE IS THE
 1997 EDITION OF THE STANDARD GAS CODE,
 NOT 1994.
  
 14)CLARIFY PSI FOR GAS SYSTEM.PLANS NOTE
 25 PSI?(SEE SHT.P4.)
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER