| Plan Review Notes For Permit 00050907 |
| Permit Number |
00050907 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED********************** | | | 1) AIR CONDITIONING AND AIR BALANCE OK | | | | | | 2) PROVIDE DETAIL ON KITCHEN GREASE EX- | | | HAUST DUCT PATH OF TRAVEL FROM KITCHEN | | | TO OUTSIDE OF BUILDING | | | | | | 1997 SMC 505.9.1 VERTICAL AND HORIZONTAL | | | DUCTS LOCATED IN BUILDINGS TWO OR MORE | | | STORIES SHALL BE ENCLOSED IN A CONTIN- | | | UOUS ENCLOSURE FROM THE CEILING ABOVE | | | THE HOOD TO OR THROUGH THE ROOF. | | | SMC 505.9.2 REQUIRES THE ENCLOSURE TO BE | | | USED EXCLUSIVELY FOR A SINGLE GREASE | | | EXHAUST SYSTEM ANS SHALL BE USED FOR NO | | | OTHER PURPOSE. | | | NOTE: SEPARATE PERMITS REQUIRED FOR HOOD | | | WALK-IN COOLER/FREEZER AND FIRE SUPPRES- | | | SION FOR HOODS |
|