Date Text
2001-01-08 00:00:00***********DENIED**********************
 1) AIR CONDITIONING AND AIR BALANCE OK
  
 2) PROVIDE DETAIL ON KITCHEN GREASE EX-
 HAUST DUCT PATH OF TRAVEL FROM KITCHEN
 TO OUTSIDE OF BUILDING
  
 1997 SMC 505.9.1 VERTICAL AND HORIZONTAL
 DUCTS LOCATED IN BUILDINGS TWO OR MORE
 STORIES SHALL BE ENCLOSED IN A CONTIN-
 UOUS ENCLOSURE FROM THE CEILING ABOVE
 THE HOOD TO OR THROUGH THE ROOF.
 SMC 505.9.2 REQUIRES THE ENCLOSURE TO BE
 USED EXCLUSIVELY FOR A SINGLE GREASE
 EXHAUST SYSTEM ANS SHALL BE USED FOR NO
 OTHER PURPOSE.
 NOTE: SEPARATE PERMITS REQUIRED FOR HOOD
 WALK-IN COOLER/FREEZER AND FIRE SUPPRES-
 SION FOR HOODS