2001-01-08 00:00:00FIRE ALARM SYSTEM SHALL BE CLASS "A" OR
 ADDRESSABLE.
  
 HOOD EXTINGUISHING SYSTEM SHALL BE
 INTERCONNECTED WITH FIRE ALARM SYSTEM.
  
 INTERIOR FINISH SHALL BE CLASS A OR B.
  
 PROVIDE AN APPROVED,RATED CURTAIN IN THE
 DOORWAY OF THE PRIVATE ROOM. CURTAIN
 SHALL BE IN ACCORDANCE WITH NFPA 701.