Plan Review Notes
Plan Review Notes For Permit 00050907
Permit Number 00050907
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATINGS
 OF 600 AMP DISC AND 700AMP BREAKER.
 MAINS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT.MUST BE PLANS 215-5
  
 2)NOTE: PLEASE NOTE AS PER LOCAL CODE
 OUTLET SPACING TO BE EVERY 20` OF
 UNENCUMBERED WALL SPACE. 210-50 SEE E-3
 CLOUDED AREA .
  
 3)NOTE: PLEASE NOTE ART 450-21B FOR
 TRANSFORMER ROOM REQ`MENTS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372
  
  
 PLEASE SHOW CHEFS PANEL LOCATION.