| Plan Review Notes For Permit 00050907 |
| Permit Number |
00050907 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATINGS | | | OF 600 AMP DISC AND 700AMP BREAKER. | | | MAINS MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT.MUST BE PLANS 215-5 | | | | | | 2)NOTE: PLEASE NOTE AS PER LOCAL CODE | | | OUTLET SPACING TO BE EVERY 20` OF | | | UNENCUMBERED WALL SPACE. 210-50 SEE E-3 | | | CLOUDED AREA . | | | | | | 3)NOTE: PLEASE NOTE ART 450-21B FOR | | | TRANSFORMER ROOM REQ`MENTS. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 | | | | | | | | | PLEASE SHOW CHEFS PANEL LOCATION. |
|