| Plan Review Notes For Permit 00050907 |
| Permit Number |
00050907 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *****BUILDING REVIEW COMMENTS***** | | | | | | 1]SUBMIT PRODUCT TESTS FOR ANY NEW EXTER | | | IOR DOORS AND WINDOWS,PROVIDE IMPACT | | | PROTECTION METHOD FOR EXTERIOR GLAZING | | | 2]ENERGY CALCULATIONS ARE REQUIRED. | | | 3]SPECIFY ALL HAZARDOUS LOCATIONS FOR | | | GLAZING,SEE 2405.2,SBC. | | | 4]TABLE 1004,SBC,REQUIRES CORRIDOR AND | | | ISLE WIDTH TO BE MIN.44"CLEAR,FOR | | | OCCUPANCY OVER 50 PERSONS. | | | 5]CLERIFY [B] RATING FOR DOORS 121A AND | | | 121B,ALSO DOOR 121B SHALL PROVIDE 18" | | | CLEAR ON PULL SIDE OF HANDLE. | | | 6]PROVIDE ACCESSIBLE SEATING AT PATIO. | | | 7]SUBMIT EXITING CALCULATIONS FOR # OF | | | PERSONS EXITING FROM THE RESTAURANTS | | | AND THE BUILDING THRU THE VESTIBULE. | | | 8]HEALTH DEPARTMENT APPROVAL REQUIRED. | | | 9]SUBMIT FIRE SPRINKLER LAYOUT,PATIO | | | SEATING AREA MUST BE PROTECTED. |
|