| Plan Review Notes For Permit 00050848 |
| Permit Number |
00050848 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)DRINKING FOUNTAINS SHALL COMPLY W/ | | | FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING AND STOOPING. | | | | | | 2)PAN DRAINS ARE REQUIRED FOR THE HEATER | | | PANS.TERMINATION OF DRAINS SHALL | | | COMPLY W/SPC SEC.507.8.3.MIN.SIZE OF PAN | | | DRAIN SHALL BE MIN.1".SPC 507.8.2. | | | | | | 3)AN ADDITIONAL LAVATORY IS REQD.IN THE | | | WOMEN'S TOILET ROOM PER SPC TABLE 407. | | | SEE SPACES #1,#7. | | | | | | 4)A MIN.OF 29" IS REQD.UNDER THE H.C. | | | LAVS.FACBC SEC.4.19.2.SEE SHT.TI-A3. | | | | | | 5)WATER CLOSETS AND LAVS.IN UNITS #4 & 5 | | | ARE NOT PROPERLY VENTED.SPC SEC.901.2, | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|