| Plan Review Notes For Permit 00050848 |
| Permit Number |
00050848 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW: | | | 1). S.B.C.1606.2.6.2. COMPONENTS & | | | CLADDING. 1606.3.1 ROOF DECKS. | | | ALL WALLS AND ROOF FRAMING INCLUDING | | | CLADDING AND CONNECTIONS OF THESE | | | ELEMENTS. THERE IS NO INFORMATION ON HOW | | | THE 2X6 FRAMING MEMBERS ARE ATTACHED TO | | | THE EXISTING ROOF AND FRAMING MEMBERS. | | | ADMIN. CODE 104.2.2 ADDITIONAL INFO. ON | | | THE ALUM. LOUVERED SCREEN WALL,ANCHORAGE | | | AND WIND LOAD DATA SHOULD BE INCORPARA- | | | TED INTO THE ANCHORAGE OF THE 2X6 DECK | | | SYSTEM. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|