| 2001-01-08 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT |
| | #`S ON PLANS TO CORRELATE WITH PANEL |
| | SCHEDULES. |
| | |
| | 2)NOTE: PLEASEINCLUDE THE RISER DIA- |
| | -GRAM FOR BLDG. 'B'. PLEASE SHOW MAIN/ |
| | DISC,GROUNDING,ETC. 215-5 AIC RATING FOR |
| | MAIN PER 110-9 |
| | |
| | 3)NOTE:PLEASE REMOVE COMMENT ON RISER |
| | DIAGRAM FOR BLDG. 'A' THAT SHOWS PANEL#7 |
| | THIS IS TO BE ON SEPARATE RISER DIAGRAM. |
| | |
| | 4)NOTE: PLEASE SEE SIZING FOR GROUNDING |
| | ELECTRODE CONDUCTOR PER 250-66 |
| | |
| | 5)NOTE: PLEASE SHOW THE HOUSE PANEL AND |
| | METER FOR BLDG. 'A'.ON RISER DIAGRAM FOR |
| | BLDG.'B'. SERVICES MUST BE BONDED. |
| | |
| | 6)NOTE: PLEASE SHOW THE REQ`D GFI RECEPT |
| | FOR CU ON BLDG.'B'. |
| | |
| | 7)NOTE: OUTSIDE LIGHTING FOR BLDG 'B' |
| | SHOWS GOING TO PANEL VIA TC? SHOW PANEL |
| | FEED FOR LIGHTING. |
| | |
| | 8)NOTE:SHOW ALL OUTSIDE LIGHTING FOR BLD |
| | 'A' BRANCH CIRCUIT #`S |
| | |
| | 9)NOTE:PLEASE PLACE TWO NOTES ON PLANS,, |
| | ONE FOR CLEARENCES FOR A/C CU`S PER ART; |
| | 110-26 AND SECOND NOTE ON RISER DIAGRAM |
| | FOR ART; 230-2-E IDENTIFICATION OF |
| | SERVICE MAINS. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. 659-8096 EXT 8372 |