Plan Review Notes
Plan Review Notes For Permit 00050833
Permit Number 00050833
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00*****************PROVISO****************
  
 1)DETAILS AND CALCULATIONS SHALL BE
 SUBMITTED FOR SECONDARY ROOF DRAINAGE
 SYSTEM.COMPLY W/SPC SECX.1109.1-1109.3
 AND APPENDIX"A".INCLUDE 1/2 THE AREA OF
 THE PARAPET WALL PER SPC SEC.1108.3.
 SHOW THE CALCULATIONS PER THE ABOVE
 NOTED CODE SECTIONS AND SIZE THE
 SCUPPERS ACCORDINGLY.THE SCUPPERS FOR
 THE HIGH ROOF ARE DRAINING ONTO THE LOW
 ROOF.WHERE IS THE SECONDARY DRAINAGE
 FOR THE LOW ROOF?PROVIDE CALCULATIONS
 THAT THE 2-4" ROOF DRAINS WILL HANDLE
 THE ADDITIONAL LOAD.PLANS SHALL BE
 SUBMITTED FOR REVIEW WITHIN 7 DAYS.