| Plan Review Notes For Permit 00050833 |
| Permit Number |
00050833 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | AS PREVIOUSLY REQUESTED-SUBMIT DETAILS | | | AND CALCULATIONS FOR SECONDDARY ROOF | | | DRAINAGE SYSTEM.COMPLY W/SPC SEC.1109.1- | | | 1109.3 AND APPENDIX "A".INCLUDE 1/2 THE | | | AREA OF THE PARAPET WALL PER SPC 1108.3. | | | SHOW THE CALCULATIONS PER THE ABOVE | | | NOTED CODE SECTIONS AND SIZE THE | | | SCUPPERS ACCORDINGLY.THE SCUPPERS ARE | | | SHOWN DRAINING ONTO THE LOW ROOF.WHERE | | | IS THE SECONDARY SYSTEM FOR THIS AREA & | | | PROVIDE CALCULATIONS THAT THE 2-4"ROOF | | | DRAINS WILL HANDLE THE ADDITIONAL LOAD. |
|