Date Text
2001-01-08 00:00:00AS PREVIOUSLY REQUESTED-SUBMIT DETAILS
 AND CALCULATIONS FOR SECONDDARY ROOF
 DRAINAGE SYSTEM.COMPLY W/SPC SEC.1109.1-
 1109.3 AND APPENDIX "A".INCLUDE 1/2 THE
 AREA OF THE PARAPET WALL PER SPC 1108.3.
 SHOW THE CALCULATIONS PER THE ABOVE
 NOTED CODE SECTIONS AND SIZE THE
 SCUPPERS ACCORDINGLY.THE SCUPPERS ARE
 SHOWN DRAINING ONTO THE LOW ROOF.WHERE
 IS THE SECONDARY SYSTEM FOR THIS AREA &
 PROVIDE CALCULATIONS THAT THE 2-4"ROOF
 DRAINS WILL HANDLE THE ADDITIONAL LOAD.