| Plan Review Notes For Permit 00050833 |
| Permit Number |
00050833 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)LAVATORIES ARE REQD.IN THE HANDICAP | | | STALLS ON THE 2ND.LEVEL.FACBC SEC.4.17.3 | | | | | | 2)SHOW THE LENGTH AND WIDTH OF THE | | | HANDICAP STALLS ON THE FIRST AND SECOND | | | LEVELS.COMPLY W/FACBC SEC.4.17.3.AND | | | FIG.30.(MIN.WIDTH SHALL NOT BE LESS THAN | | | 83".) | | | | | | 3)SUBMIT DETAILS AND CALCULATIONS FOR | | | SECONDARY ROOF DRAINAGE SYSTEM.COMPLY W/ | | | SPC SEC.1109.1-1109.3.AND APPENDIX "A". | | | | | | 4)SUBMIT DETAIL OF GREASE TRAP.COMPLY | | | W/CITY OF WPB REQS.(SEE ATTACHED). | | | SUBMIT APPROVAL FORM FROM CITY OF WPB | | | UTILITIES.CONTACT R.COMPO AT 561-835- | | | 7423. | | | | | | 5)WATER CLOSETS NOT PERMITTED ON WET | | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | | SEC.911.1.1. | | | | | | 6)CLEANOUTS IN BLDG.SEWER SHALL BE | | | SPACED PER SPC 710.2.4. | | | | | | 7)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | IF YOU HAVE ANY QUESTIONS CALL | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER |
|