| Date |
Text |
| 2001-01-08 00:00:00 | FAILED |
| | TOO MANY COMMENTS MUST BE ADDRESSED |
| | 1- 6" GRAVITY SEWER LATERALS REQUIRED ON |
| | CITY ROW.4" IS ALLOWED ON PRIVATE |
| | PROPERTY. |
| | 2- SHOW SIZES OF EXISTING DIP WM AS BEIN |
| | G 6" AND PLACE NOTE TO BE FIELD VERIFIED |
| | 3- PLACE METER ON SIDEWALK |
| | 4- PLEASE SHOW FULL EXTENT OF ALL SANITA |
| | RY LINES AND WATER LINE UP TO THE BUILDI |
| | NG. MEASURE AND SEE IF ANY DEP PERMITS |
| | WILL BE REQUIRED. |
| | 5-CORRECT DIRECT TAP NOTE TO REFLECT |
| | EXISTING PIPE SIZE THAT YOU WILL BE |
| | CONNECTING TO. |
| | 6- SDR 26 PVC IS THE MINIMUM REQUIREMENT |
| | FOR SANITARY SEWER SERVICES OUT IN R.O.W |
| | 7- PROVIDE ON PLAN THE SUNSHINE LOCATING |
| | NOTE 1 800 432 4770 |
| | 8- PLEASE PROVIDE ON PLAN THE PERVIOUS |
| | AND IMPERVIOUS INFORMATION IN ACRES AND |
| | IN SQUARE FEET. |
| | 9- SHOW POLLUTION CONTROL FENCE AROUND |
| | CONSTRUCTION SITE AND POLLUTION CONTROL |
| | DEVICES. |
| | 10- THE 6" STUB MUST BE INSTALLED AFTER |
| | DDCV. (SEE PLAN) |
| | AFTER PLAN HAS BEEN SUBMITTED PLEASE |
| | FILL THE PRODUCT SUBMITTAL LIST AND |
| | RETURN TWO COPIES ONE FOR OUR INSPECTOR |
| | AND ON FOR THE FILE. |
| | ANY QUESTIONS MAY BE DIRECTED TO MANNY |
| | GONZALEZ AT PUBLIC UTILITIES |
| | 1000 45TH STR WPB FL 33407 |
| | 561 659 8040 PLEASE RETURN MARK-UP |
| | ALONG WITH THE TWO NEW REVISED SETS. |