Plan Review Notes
Plan Review Notes For Permit 00050833
Permit Number 00050833
Review Stop ENG
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00FAILED
 TOO MANY COMMENTS MUST BE ADDRESSED
 1- 6" GRAVITY SEWER LATERALS REQUIRED ON
 CITY ROW.4" IS ALLOWED ON PRIVATE
 PROPERTY.
 2- SHOW SIZES OF EXISTING DIP WM AS BEIN
 G 6" AND PLACE NOTE TO BE FIELD VERIFIED
 3- PLACE METER ON SIDEWALK
 4- PLEASE SHOW FULL EXTENT OF ALL SANITA
 RY LINES AND WATER LINE UP TO THE BUILDI
 NG. MEASURE AND SEE IF ANY DEP PERMITS
 WILL BE REQUIRED.
 5-CORRECT DIRECT TAP NOTE TO REFLECT
 EXISTING PIPE SIZE THAT YOU WILL BE
 CONNECTING TO.
 6- SDR 26 PVC IS THE MINIMUM REQUIREMENT
 FOR SANITARY SEWER SERVICES OUT IN R.O.W
 7- PROVIDE ON PLAN THE SUNSHINE LOCATING
 NOTE 1 800 432 4770
 8- PLEASE PROVIDE ON PLAN THE PERVIOUS
 AND IMPERVIOUS INFORMATION IN ACRES AND
 IN SQUARE FEET.
 9- SHOW POLLUTION CONTROL FENCE AROUND
 CONSTRUCTION SITE AND POLLUTION CONTROL
 DEVICES.
 10- THE 6" STUB MUST BE INSTALLED AFTER
 DDCV. (SEE PLAN)
 AFTER PLAN HAS BEEN SUBMITTED PLEASE
 FILL THE PRODUCT SUBMITTAL LIST AND
 RETURN TWO COPIES ONE FOR OUR INSPECTOR
 AND ON FOR THE FILE.
 ANY QUESTIONS MAY BE DIRECTED TO MANNY
 GONZALEZ AT PUBLIC UTILITIES
 1000 45TH STR WPB FL 33407
 561 659 8040 PLEASE RETURN MARK-UP
 ALONG WITH THE TWO NEW REVISED SETS.