| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT DETAILS ON THE TYPES OF FUNCTIONS |
| | AND ACTIVITIES TAKING PLACE IN THE |
| | STRUCTURE.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1. |
| | |
| | LAVATORIES ARE REQD.WITHIN THE H.C. |
| | ACCESSIBLE STALLS PER FACBC SEC.4.17.3. |
| | |
| | SIZE OF ACCESSIBLE STALLS SHALL COMPLY |
| | W/FACBC SEC.4.17.3. |
| | |
| | A H.C.ACCESSIBLE STALL IS REQD.IN EACH |
| | TOILET ROOM PER FACBC 4.1.3.(11). |
| | (UNISEX TOILET ROOM WILL NOT SUFFICE) |
| | |
| | TOILET ROOMS SHALL HAVE WAINSCOTING UP |
| | TO 4' PER SBC SEC.1204.2. |
| | |
| | SHT.ME-2-SHOWS 6"ROOF DRAIN LINE |
| | DRAINING INTO 4"LINE.COMPLY W/SPC 307.5, |
| | 709.1,709.2. |
| | |
| | SUBMIT COMPLETE STORM DRAINAGE ISOMETRIC |
| | SHOWING SQ.FT.AREA OF ROOF DRAINED BY |
| | EACH DRAIN AND PROVISIONS FOR SECONDARY |
| | (EMERGENCY )DRAINAGE. |
| | |
| | SHT.P1-WATER SERVICE AND SEWER CANNOT BE |
| | RUN IN THE SAME TRENCH PER SPC 307.5. |
| | |
| | CONTACT CITY OF WEST PALM BEACH UTILITY |
| | DEPT.FOR GREASE TRAP APPROVAL.SUBMIT |
| | COPY OF APPROVAL FORM.CONTACT R.COMPO |
| | AT 835-7423. |
| | |
| | DISHWASHER SHALL DISCHARGE TO SANITARY |
| | PER CITY OF WPB ORDINANCE. |
| | |
| | PVC INSTALLED ON ROOF SHALL BE SUPPORTED |
| | AT 4' INTERVALS PER SPC SEC.310.3.6. |
| | |
| | SHT.P4-2ND.FLR.SANITARY-DRY VENTS NOT |
| | PERMITTED PER SPC 906.2.1. |
| | |
| | WATER CLOSET NOT PERMITTED ON WET VENT |
| | PER COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 911.1.1. |
| | |
| | A PERMIT MAY BE REQD.FROM DEPT.OF |
| | ENVIRONMENTAL PROTECTION FOR THE WATER |
| | AND SEWER LINES. |