| Plan Review Notes For Permit 00050833 |
| Permit Number |
00050833 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1) EXHAUST FAN #7 SERVES FIRST FLOOR | | | SPACE, INTERLOCKED WITH SECOND FLOOR | | | EQUIPMENT. INTERLOCK TO EQUIPMENT WHICH | | | SERVES FLOOR INVOLVED. | | | 2) EQUIPMENT UNIT DATA CONFLICTS WITH | | | VOLUME OF AIR DELIVED TO SPACE. CORRECT | | | TO REFLECT EQUIPMENT MATCHING SPACE | | | REQUIREMENTS | | | 3) AIR CONDITIONING UNIT DATA SHOWS | | | UNIT #5 AND #6. THESE UNITS ARE NOT | | | INDICATED ON PLAN. WHAT AREAS DO THESE | | | SERVE? | | | 4) PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2 |
|