| Plan Review Notes For Permit 00050833 |
| Permit Number |
00050833 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | | | | | | | 1.FIRE ALARM SYSTEM SHALL BE CLASS "A" | | | OR ADDRESSABLE.PROVIDE SPEAKER STROBES | | | IN EACH SECOND FLOOR MEETING ROOM. | | | 2.KITCHEN HOOD EXTINGUISHING SYSTEM | | | SHALL BE CONNECTED TO THE FIRE ALARM | | | SYSTEM. | | | 4. INTERIOR FINISH SHALL THROUGHOUT | | | SHALL BE CLASS A OR B. | | | 5.PROVIDE PANIC HARDWARE ON ALL | | | DESIGNATED EXIT DOORS SUBJECT TO 100 OR | | | MORE PERSONS.(PARISH HALL,NORTH & SOUTH | | | EXIT CORRIDORS,&DOORS LEADING TO STAIRS) | | | 6. DOORS 36 AND 37 SHALL SWING IN THE | | | DIRECTION OF EXIT TRAVEL. |
|