| 2001-01-08 00:00:00 | PROVIDE WATER AND SEWER PLAN SHOWING |
| | THE FOLLOWING ITEMS: |
| | CONNECTIONS OF WATER SERVICE WILL BE |
| | THRU DIRECT TAPS ONLY. PROVIDE SIZE |
| | (NO TAPPING SADDLES WILL BE ALLOWED) |
| | SHOW EXIST. METER LOCATION AND NOTE |
| | METER TO BE SHUT OFF, CUT AND PLUGGED. |
| | |
| | NEW METER LOCATION MUST BE JUST OUT SIDE |
| | OF RIGHT OF WAY ON THE SIDEWALK WITH |
| | LOCKING METER BOX LID AND TOUCH READ |
| | HOLE.THE DOUBLE CHECK DETECTOR ASSEMBL |
| | Y MUST JUST INSIDE PROPERTY LINE/R.O.W. |
| | LINE. |
| | |
| | SHOW EXISTING WATER AND SEWER LINE |
| | LOCATIONS ALONG SAQUOIA DRIVE. |
| | FOR LOCATION OF THESE LINE YOU MAY |
| | CONTACT OUR CAD DEPARTMENT AT 659-8040 |
| | EXT. 2303 |
| | FOR SEWER CONNECTION YOU MAY CONNECT TO |
| | EXISTING SANITARY SEWER SERVICE LINE IF |
| | IT IS 6" OR HIGHER, THIS WOULD COST |
| | EFFECTIVE TO THE PROPERTY OWNER. |
| | |
| | AN 18" MINIMUM SEPARATION IS REQUIRED |
| | BETWEEN ALL WATER AND SEWER. |
| | |
| | A 6" MINIMUM SEPERATION WILL BE REQUIRED |
| | BETWEEN SANITARY AND STORM. |
| | |
| | WHEN CONNECTION NEW SEWER SERVICE TO |
| | NEW PARISH HALL THE BATHROOMS CONNECTION |
| | S MUST BE CONNECTED AFTER THE GREASE |
| | TRAP.A CLEAN OUT WILL BE REQUIRED AT |
| | EVERY TURN OR EVER 100 L.F. OF STRAIGHT |
| | RUN. A CLEAN OUT IS REQUIRED JUST INSIDE |
| | OF PROPERTY LINE. |
| | NO STORM PLAN HAS BEEN SUBMITTED. |
| | SEE ATTACHED OUR STORM WATER UTILITY |
| | REQUIREMENTS. |
| | |
| | SINCE THERE IS A MINIMAL AMOUNT OF STORM |
| | YOU MAY INCLUDE IT IN WATER AND SEWER |
| | PLAN. |
| | |
| | YOU MUST ALSO PROVIDE THE CITY'S |
| | STANDARD DETAILS THAT MAY APPLY. EITHER |
| | CREATE A NEW SHEET OR YOU MAY INCLUDE |
| | THEM ON THIS SHEET IF THEY FIT. |
| | |
| | ONCE PLANS HAVE BEEN APPROVED THE |
| | CONTRACTOR MUST SUPPLY SHOP DRAWINGS |
| | FOR APPROVAL BY CITY OF WEST PALM BEACH |
| | PUBLIC UTILITIES ENGINEERING DEPARTMENT |
| | ATTENTION MANNY GONZALEZ, PROJECT SPECIA |
| | LIST. LOCATION: 1000 45TH ST. SUITE 9 |
| | WEST PALM BEACH, FL 33407 (561) 659-8040 |
| | EXT. 2306 |
| | |
| | ALL PAVEMENT CUT TO INSTALL SERVICES |
| | MUST BE NOTED AND REFERENCED TO THE |
| | OUR STANDARD PAVEMENT REPLACEMENT DETAIL |
| | |
| | THE WATER SEWER AND DRAINAGE MUST BE |
| | DESIGNED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED CIVIL ENGINEER. |